7202 Model 900 Service Clearances

The broken lines of the footprint indicate the amount of space needed by the unit during normal operation.
For multiple racks placed side by side, the left and right clearances apply only to the leftmost and
rightmost rack. For five to six racks placed side by side, the left and right clearances need to be increased
to 1525 mm (60 in). Having more than six racks side by side is not recommended.
Note: Rack units are large and heavy, and they are not easily moved. Because maintenance activities
require access at both the front and back, extra room must be allowed. The footprint shows the
radius of the swinging door on the rear of the rack and a drawer in the extended position. The
illustration shows the minimum space required.
280
Site and Hardware Planning Information