7015 Powerserver 970B And 980B - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

7015 POWERserver 970B and 980B

Dimensions
Height
Width
Depth
Weight
Minimum
Maximum
Electrical⁵
Power source loading (max)
Voltage range (V ac)
Frequency (hertz)
Thermal output (max)
Power requirements (max)
Power factor⁴
Inrush current⁶
Maximum altitude
Temperature Requirements
Humidity (Noncondensing)
Without tape drive
With tape drive
Wet Bulb Requirements
Without tape drive
With tape drive
1,2
Noise Emissions
L
WAd
L
pAm
<L
>
pA
m
Impulsive or prominent discrete tones
Clearances³
Install/Air Flow
Service
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
2. Noise emissions data for the 7015 system unit is based on the following configuration: a processor drawer with
eight memory cards and eight I/O cards, a SCSI device drawer with four SCSI devices, the second eight I/O slots
with eight asynchronous cards, two SCSI disk drawers with four SCSI devices each, and a battery backup unit.
Noise emissions data for the SCSI disk drawer is therefore included in the data.
3. For multiple racks placed side by side, the left and right clearances apply only to the leftmost and rightmost rack.
For five to six racks placed side by side, the left and right clearances need to be increased to 1525 mm (60 in).
Having more than six racks side by side is not recommended. See "7015 System Rack R00" on page 41 for
additional clearance information.
4. Power factor is 0.7 to 0.9 without a battery backup unit.
5. The figures for power source loading, thermal output, and power requirement represent maximums. Work with
your sales or service representative to determine the typical figures for your configuration.
6. Inrush currents occur only at initial application of power, no inrush occurs during normal use.
1578 mm
650 mm
921 mm
205kg
441kg
Maximum Entry
Configuration
1.0
200 to 240 or -48V dc
50 or 60
2165 Btu/hr
634 watts
0.5 to 0.7
125 amps
2135 m (7000 ft.)
Operating
10 to 40°C
(50 to 104°F)
Operating
8 to 80%
20 to 80%
27°C (80°F)
23°C (73°F)
Operating
6.4 bels
N/A
49 dBA
No
Front
Maintenance of a proper service clearance should allow proper air flow
(See service clearances for the "7015 System Rack R00" on page 41)
62.0 in.
25.5 in.
36.0 in.
450 lbs.
970 lbs.
Configuration
200 to 240 or -48V dc
2135 m (7000 ft.)
Non-Operating
(50 to 125°F)
Non-Operating
Back
Left
Chapter 2. Physical Characteristics of Systems
Maximum
2.4
50 or 60
4100 Btu/hr
1200 watts
0.5 to 0.7
125 amps
10 to 52°C
8 to 80%
20 to 80%
27°C (80°F)
27°C (80°F)
Idle
6.2 bels
N/A
47 dBA
No
Right
37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7006 42tEserver pseries7006 42w7007 powerportable n407008 powerstation m207008 powerstation m2a ... Show all

Table of Contents