3590 Magstar Tape System
3590 Magstar Tape System Models B11 and B1A
Dimensions
Height
Width
Depth
Weight
Electrical
Power source loading
(typical in kVA)
Thermal output
(typical)
Temperature Requirements
(media in use)
Humidity Requirements
(Noncondensing)
Wet Bulb
3590 Magstar Tape System Model C12 Frame
Dimensions
Height
Width
Depth
Weight
Electrical
Power source loading
(typical in kVA)
Thermal output
(typical)
Temperature Requirements
(media in use)
Humidity Requirements
(Noncondensing)
Wet Bulb
Note: * Includes four B1A or E1A drives and associated cables
256
Site and Hardware Planning Information
B11 Rack
522 mm 20.6 in.
230 mm 9.1 in.
988 mm 39.0 in.
49.5 kg 109 lbs.
1803 mm 71.0 in.
724 mm 28.5 in.
775 mm 30.5 in.
400 kg 880 lbs.
7830 Btu/hr *
B1A Library
262 mm 10.5 in.
221 mm 8.8 in.
750 mm 29.8 in.
28.6 kg 63 lbs.
0.3
1024 Btu/hr
16 to 32°C
(60 to 90°F)
20 to 80%
23°C (73°F)
1.2
16 to 32°C
(60 to 90°F)
20 to 80%
26°C (79°F)