Magstar Mp 3575 Tape Library Dataserver Model L06 - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

®
Magstar
MP 3575 Tape Library Dataserver Model L06
Dimensions
Height
Width
Depth
Weight
Maximum
Electrical
Power source loading
(typical in kVA)
Voltage range (V ac)
Frequency (hertz)
Thermal output
(typical)
Power requirements
(typical)
Power factor
Maximum altitude
Temperature
Requirements
Humidity
Requirements
(Noncondensing)
Wet Bulb
Noise Emissions*
L
WAd
L
pAm
<L
>
pA
m
Impulsive noise
Prominent discrete
tones
Clearances
Install/Air Flow
76 mm (3 in)
Service
Install so that it can be moved to an area providing 760 mm (30 in) on each side.
* See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
991 mm
355 mm
836 mm
71 kg
Operating
16 to 32°C
(60 to 90°F)
Operating
8 to 80%
26°C(79°F)
Operating
6.6 bels
N/A
47dBA
Yes
No
Front
Back
76 mm (3 in)
39 in.
14 in.
37.9 in.
157 lbs
0.175
100 to 127 or 200 to 240
50 or 60
600 Btu/hr
175 watts
0.99
2135 m (7000 ft.)
Left
76 mm (3 in)
Chapter 6. Physical Characteristics of the 3000 Series
Non-Operating
10 to 43°C
(50 to 110°F)
Non-Operating
8 to 80%
27°C(80°F)
Idle
5.6 bels
N/A
34dBA
Yes
No
Right
76 mm (3 in)
251