7137 Disk Array Subsystem Models 512, 513, 514, And 515 - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

7137 Disk Array Subsystem Models 512, 513, 514, and 515

Dimensions
Height
Width
Enclosure
Depth
Weight
Empty
Maximum
Configuration
Electrical
Power source loading
(kVA)
Voltage range (V ac)
Frequency (hertz)
Thermal output
Power requirements
Power factor
Maximum altitude
Temperature
Requirements
Humidity
Requirements
(Noncondensing)
Wet Bulb
,
Noise Emissions¹
²
L
WAd
L
pAm
<L
>
pA
m
(4.5GB)
Impulsive or
prominent discrete
tones
1. See "Noise Emission Notes" on page 336 for definitions of emissions positions.
2. The value for <L
>
pA
m
Operating
10 to 40°C
(50 to 110°F)
Operating
8% to 80%
23°C (73°F)
Operating
5.9 bels
N/A
39 dBA
44 dBA
No
not available at the time of publishing.
178 mm
7.0 in.
483 mm
19.0 in.
716 mm
28.2 in.
32 kg
70 lbs.
35 kg
76 lbs.
0.33
100 to 125 or 200 to 240
50 or 60
1050 Btu/hr
308 watts
0.9
2134m (7000 ft.)
Chapter 7. Physical Characteristics of the 7100 Series
Non-Operating
1 to 52°C
(34 to 125°F)
Non-Operating
8% to 80%
27°C (80°F)
Idle
5.8 bels
N/A
38 dBA
(See Note 2)
No
277

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7006 42tEserver pseries7006 42w7007 powerportable n407008 powerstation m207008 powerstation m2a ... Show all

Table of Contents