7013 Powerstation And Powerserver 52H - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

7013 POWERstation and POWERserver 52H

Dimensions
Height
Width
Depth
Weight
Minimum
Maximum
Electrical
Power source loading
(typical in kVA)
Voltage range (V ac)
Frequency (hertz)
Thermal output
(typical)
Power requirements
(typical)
Power factor
Inrush current
Maximum altitude
Temperature
Requirements
Humidity
Requirements
(Noncondensing)
Without tape drive
With tape drive
Wet Bulb
Requirements
Without tape drive
With tape drive
Noise Emissions¹
L
WAd
L
pAm
<L
>
pA
m
Impulsive or
prominent discrete
tones
Clearances
Install/Air Flow²
Service
Install so that it can be moved to an area providing 760 mm (30 in) on each side.
2
Footprint
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
2. The amount of space needed by the unit during normal operation is indicated by the footprint dimensions.
22
Site and Hardware Planning Information
610 mm
360 mm
675 mm
36.7 kg
53.1 kg
100 to 125 or 200 to 240 (autoranging)
22 amps at 120 V ac, 44 amps at 240 V ac
Operating
16 to 32°C
(60 to 90°F)
Operating
8 to 80%
20 to 80%
27°C (80°F)
23°C (73°F)
Operating
5.7 bels
N/A
39 dBA
No
Front
Back
N/A
152mm(6 in)
Width
512mm(20.2 in)
24.0 in.
14.2 in.
26.6 in.
81 lbs.
117 lbs.
0.4
50 or 60
975 Btu/hr
285 watts
0.8 to 1.0
2135 m (7000 ft.)
Non-Operating
Non-Operating
Left
76mm(3 in)
828mm(32.6 in)
10 to 43°C
(50 to 110°F)
8 to 80%
20 to 80%
27°C (80°F)
27°C (80°F)
Idle
5.5 bels
N/A
38 dBA
No
Right
76mm(3 in)
Depth