Enterprise Server Models S70 and S7A (7017, 7013, 7015)
System Rack
Dimensions
Height
Width
Depth
Weight
Minimum
(Configuration
dependant)
Electrical
Power source loading
(maximum in kVA)
Voltage range (V ac)
Frequency (hertz)
Thermal output
(Maximum)
Power requirements
(Maximum)
Power factor
Inrush current³
Maximum altitude
Temperature
4,5
Requirements
Humidity
Noncondensing
Wet Bulb
Requirements⁶
1,2
Noise Emissions
L
WAd
L
pAm
<L
>
pA
m
Impulsive or prominen
discrete tones
Clearances
Install/Air Flow
Maintenance of a proper service clearance should allow proper air flow.
Service
See "Service Clearances for System in an S70, S7A, or S80 I/O Rack" on page 54.
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
2. Noise emissions data for Models S70 and S7A are based on a system with the doors closed.
3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
4. The use of the PCI SSA Multi-Initiater/RAID EL in the Model S70 I/O Drawer limits the system usage to a 28°C
(82°F) environment maximum.
5. The upper limit of the dry bulb temperature must be derated 1 degree C per 137M (450 ft.) above 1295M (4250
ft.)
6. The upper limit of the wet bulb temperature must be derated 1 degree C per 274M (882 ft.) elevation above
1370M (4500 ft.)
46
Site and Hardware Planning Information
1577 mm
567 mm
1041 mm
400 kg
Operating
10 to 37.8°C
(50 to 100°F)
Operating
8 to 80%
23°C (73°F)
Operating
7.0 bels
N/A
N/A
No
Front
Back
62.0 in.
22.3 in.
40.9 in.
880 lbs.
1.887KVA
200 to 240
50 - 60
5796 Btu/hr
1698 watts
0.9
102 amps
2135 m (7000 ft.)
Non-Operating
Non-Operating
Left
1 to 60°C
(34 to 140°F)
8 to 80%
23°C (73°F)
Idle
7.0 bels
N/A
N/A
No
Right