7026 Model M80 CEC Drawer

The Model M80 includes the Central Electronics Complex (CEC) Drawer with an I/O Drawer. For technical
information on the I/O Drawer, see "I/O Drawer 5 EIA" on page 79.
Dimensions
Height
Width
Depth
Weight
Minimum
Maximum
Electrical
Power source loading typical in kVA
Power source loading maximum in kVA
Voltage range (V ac)
Frequency (hertz)
Thermal output (typical)
Thermal output (maximum)
Power requirements (typical)
Power requirements (maximum)
Power factor
Inrush current³
Maximum altitude
Temperature Requirements
Humidity (Noncondensing)
Without tape drive
With tape drive
Wet Bulb Requirements
Without tape drive
With tape drive
1,2
Noise Emissions
With M80 CEC Drawer only
L
WAd
L
pAm
<L
>
pA
m
Impulsive or prominent discrete tones
1,2
Noise Emissions
With M80 and Primary I/O Drawer
L
WAd
L
pAm
<L
>
pA
m
Impulsive or prominent discrete tones
Install/Air Flow Clearance
Service Clearance
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
2. Noise emissions data are based on the following configuration: a drawer is in a T00 Rack and a power
distribution unit is installed in the rack and the system is operating in a normal environment of 25 °C (78 °F)
3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
78
Site and Hardware Planning Information
355.6 mm
445.5 mm
825.5 mm
69.7 kg
74.6 kg
Operating
10 to 40°C
(50 to 104°F)
Operating
8 to 80%
20 to 80%
27°C (80°F)
27°C (80°F)
Operating
6.4 bels
N/A
48 dBA
No
Operating
6.5 bels
N/A
49 dBA
No
Maintenance of a proper service clearance should allow proper air flow.
(See service clearances for the 7014 T00 Rack)
14.0 in.
17.5 in.
32.5 in.
158 lbs.
169 lbs.
0.39
0.6
200 to 240
50 or 60
1265 Btu/hr
1877 Btu/hr
370 watts
550 watts
0.95
34 amps
2135 m (7000 ft.)
Non-Operating (Power Off)
10 to 52°C
(50 to 125°F)
Non-Operating (Power Off)
8 to 80%
8 to 80%
27°C (80°F)
27°C (80°F)
6.4 bels
48 dBA
6.5 bels
49 dBA
Idle
N/A
No
Idle
N/A
No