7134 Model 010 High-Density Scsi Disk Subsystem - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

7134 Model 010 High-Density SCSI Disk Subsystem

Dimensions
Height
Width
Depth
Weight
Minimum
Maximum
Electrical
Power source loading
(kVA)
Voltage range (V ac)
Frequency (hertz)
Thermal output (max)
Power requirements
Power factor
Maximum altitude
Temperature
Requirements
Humidity
Requirements
(Noncondensing)
Wet Bulb
Noise Emissions*
L
WAd
L
pAm
<L
>
pA
m
Impulsive or
prominent discrete
tones
* See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
171 mm
444 mm
665 mm
69 kg
129 kg
0.021 plus 0.024 for each 2GB Disk Drive, or
0.028 for each 4.5GB Disk Drive
100 to 125 or 200 to 240 (autoranging)
68 Btu/hr plus 77 Btu/hr for each 2GB Disk Drive, or
90 Btu/hr for each 4.5 GB Disk Drive
20 watts plus 22.5 watts for each 2GB Disk Drive, or
26.5 watts for each 4.5GB Disk Drive
0.95 minimum
2135 m (7000 ft.)
Operating
10 to 40°C
(50 to 110°F)
Operating
8% to 80%
27°C (80°F)
Operating
5.8 bels
N/A
46 dBA
No
Chapter 7. Physical Characteristics of the 7100 Series
6.7 in.
(4EIA units)
17.4 in.
26.2 in.
31.5 lbs.
58.5 lbs.
50 or 60
Non-Operating
10 to 52°C
(50 to 125°F)
Non-Operating
8% to 80%
27°C (80°F)
5.6 bels
46 dBA
Idle
N/A
No
273

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7006 42tEserver pseries7006 42w7007 powerportable n407008 powerstation m207008 powerstation m2a ... Show all

Table of Contents