7026 Model 6H1 Cec Drawer - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

7026 Model 6H1 CEC Drawer

The Model 6H1 includes the Central Electronics Complex (CEC) Drawer with an I/O Drawer. For technical
information on the I/O Drawer, see "I/O Drawer 5 EIA" on page 79.
Dimensions
Height
Width
Depth
Weight
Minimum configuration
Maximum configuration
Electrical
Power source loading typical in kVA
Power source loading maximum in kVA
Voltage range (V ac)
Frequency (hertz)
Thermal output (typical)
Thermal output (maximum)
Power requirements (typical)
Power requirements (maximum)
Power factor
Inrush current¹
Maximum altitude²
Temperature Requirements²
Humidity Noncondensing
Without tape drive
With tape drive
Wet Bulb Requirements
Without tape drive
With tape drive
Noise Emissions³
With H80 CEC Drawer only
L
WAd
L
pAm
<L
>
pA
m
Impulsive or prominent discrete tones
Noise Emissions³
With H80 and Primary I/O Drawer
L
WAd
L
pAm
<L
>
pA
m
Impulsive or prominent discrete tones
Install/Air Flow Clearance
Service Clearance
218 mm 8.58 in. 5 (EIA Units)
Operating₄
10 to 40°C
(50 to 104°F)
Operating
8 to 80%
20 to 80%
27°C (80.6°F)
23°C (73°F)
Operating
5.8 bels
N/A
45 dBA
No
Operating
6.2 bels
N/A
48 dBA
No
Maintenance of proper service clearances should allow proper air flow.
(See service clearances for the 7014 T00 Rack)
445 mm 17.5 in.
820 mm 32.3 in.
41 kg 90 lbs.
52 kg 115 lbs.
0.32
0.48
200 to 240
50 or 60
1025 Btu/hr
1536 Btu/hr
300 watts
450 watts
0.95
40 amps
2135 m (7000 ft.)
Non-Operating
10 to 52°C
(50 to 125.6°F)
Non-Operating
8 to 80%
8 to 80%
27°C (80.6°F)
27°C (80.6°F)
5.8 bels
45 dBA
6.2 bels
48 dBA
Chapter 2. Physical Characteristics of Systems
Idle
N/A
No
Idle
N/A
No