7038 Model 6M2 (Eserver pSeries 650)

Dimensions
Height
Width
Depth
Weight
Electrical
Power source loading (typical)
Power source loading (max.)
Voltage range
Frequency
Thermal output (typical)
Thermal output (max.)
Power requirements (typical)
Power requirements (max.)
Power factor
Inrush current²
3, 4
Maximum altitude
Temperature Requirements³
Humidity Requirements⁴
(Noncondensing)
Wet Bulb
1, 5, 6
Noise Emissions
L
WAd
<L
>
pA
m
Install/Air Flow
Service Clearances
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions. See noise emissions note
4.
2. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
3. The upper limit of the dry bulb temperature must be derated 1°C per 137 m (450 ft.) above 915 m (3000 ft.).
4. The upper limit of the wet bulb temperature must be derated 1°C per 274 m (900 ft. ) above 305 m (1000 ft.).
5. The L
emission increases to 6.5 bels with a configuration of one 7038-6M2 and four 7311-D10 drawers.
WAd
6. The L
>
emission increases to 48 dBA with a configuration of one 7038-6M2 and four 7311-D10 drawers.
pA
m
86
Site and Hardware Planning Information
200 to 240 V ac, V dc not supported
Operating
10 to 38°C
(50 to 100°F)
Operating
8 to 80%
23°C (73°F)
Operating
5
6.1 bels
6
44 dBA
Maintenance of service clearance will allow proper air flow.
See "T00 and T42 Service Clearances and Caster Location" on page 33 for T00 or
T42 rack service clearances.
351 mm (13.8 in)
445 mm (17.5 in.)
760 mm (29.9 in.)
93 kg (205 lbs)
8-way processor: 1.126 kVA
8-way processor: 1.684 kVA
50 or 60 Hz
8-way processor: 3,652Btu/hr
8-way processor: 5,461 Btu/hr
8-way processor: 1,070 watts
8-way processor: 1,600 watts
0.95
67 amps at 200 V ac, 60 Hz
87 amps at 230 V ac, 50 Hz
3048 m (10000 ft.)
Non-Operating
1 to 43°C
(34 to 109°F)
Non-Operating
8 to 80%
27°C (81°F)
Idle
5
6.1 bels
6
44 dBA
Storage
1 to 60°C
(34 to 140°F)
Storage
5 to 80%
29°C (84.2°F)