IBM RS/60000 Series Site And Hardware Planning Information page 130

Table of Contents

Advertisement

Attention:
It is the customer's responsibility to ensure the following steps are completed before the
service representative performs the tie-down procedure.
Note: To accommodate a floor with a depth of more than 16 inches, a steel beam or a steel channel
adapter for mounting the subfloor eyebolts are required. The customer must supply the floor
eyebolts.
Consider the following when preparing the floor for tie-down:
v The hardware is designed to support a frame weighing no more than 2636 pounds.
v The estimated maximum concentrated load on one caster for a 2636 pound-system is 900 pounds. For
a multiple system installation, it is possible that one floor tile will bear a total concentrated load of 1800
pounds.
To install the eyebolts, do the following:
1. Obtain the service of a qualified structural engineer to determine appropriate installation of the
eyebolts.
2. Consider the following before installing the eyebolts:
v Floor eyebolts must be securely anchored to the concrete floor.
v The minimum height of the center of the internal diameter is 1 inch above the concrete floor surface.
v The maximum is height 2.5 inches above the concrete floor surface. Higher than 2.5 inches can
cause excessive lateral deflection to the tie-down hardware.
v The eyebolt's internal diameter should be 1 3/16 inch, and each eyebolt should be able to withstand
2700 pounds. The customer should obtain the service of a qualified consultant or structural engineer
to determine the appropriate anchoring method for these eyebolts and to ensure that the raised floor
can support the floor-loading specifications.
3. The plan for installing four eyebolts positioned to match the dimensions is given in the following
illustrations.
64.6 mm
654.8 mm
(2x) Opening for Cables
1220 mm REF
48 in REF
610 mm (24 Inch) Floor Tile Layout
112
Site and Hardware Planning Information
(4x) 49.3 mm
Eyebolt
(2x) 450 mm REF