7025 Deskside F40 Series - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

7025 Deskside F40 Series

Dimensions
Height
Width
Width with Pedestal
Depth
Depth with Pedestal
Weight
Minimum configuration
Maximum configuration
Electrical
Power source loading typical in kVA
Power source loading maximum in kVA
Voltage range (V ac)
Frequency (hertz)
Thermal output (typical)
Thermal output (maximum)
Power requirements (typical)
Power requirements (maximum)
Power factor
Inrush current³
Maximum altitude
Temperature Requirements
Humidity Requirements
(Noncondensing)
Wet Bulb
Noise Emissions¹
L
WAd
L
pAm
<L
>
pA
m
Impulsive or prominent discrete tones
Clearances
Install/Air Flow²
Service
2
Footprint
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
2. The amount of space needed by the unit during normal operation is indicated by the footprint dimensions.
3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
64
Site and Hardware Planning Information
100 to 127 or 200 to 240 (autoranging)
30 amps at 120 V ac, 60 amps at 240 V ac
Operating
16 to 32°C
(60 to 90°F)
Operating
8 to 80%
23°C (73°F)
Operating
5.8 bels
N/A
41 dBA
No
Front
76mm(3 in)
152mm(6 in)
Install so that it can be moved to an area providing 457 mm (18 in.) on the
front and 457 mm (18 in) on the left side.
Width
350mm(13.7 in)
620 mm 24.3 in.
245 mm 9.6 in.
350 mm 13.7 in.
695 mm 27.3 in.
745 mm 29.3 in.
30 kg 65 lbs.
50 kg 110 lbs.
0.41
0.56
50 or 60
1125 Btu/hr
1535 Btu/hr
330 watts
450 watts
0.8 - 0.96
2135 m (7000 ft.)
Non-Operating
(50 to 110°F)
Non-Operating
Back
Left
51mm(2 in)
975mm(38.4 in)
10 to 43°C
8 to 80%
27°C (80°F)
Idle
5.5 bels
N/A
38 dBA
No
Right
51mm(2 in)
Depth