Power And Electrical Requirements - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

system to the installation site. If the height or weight of the system can cause a problem when the system
is moved to the installation site, the customer should contact their local site planning, marketing, or sales
representative.

Power and Electrical Requirements

Dual power and line cords are standard on the Eserver pSeries 655. For maximum availability, each of
the line cords should be fed from independent power grids. Some configurations require drawing current
from two power feeds in a non-redundant manner.
The following table illustrates electrical and thermal characteristics for the Eserver pSeries 655.
Electrical/Thermal Characteristic
Rated Voltage (V ac, 3 phase)
Rated Current, Line Cord with 60-A Plug,
FC 8688 or 8689 (amps, per phase)
Rated Current, All Other Line Cords
(amps, per phase)
Frequency (Hz)
Power (Maximum in kW)
Typical, Full Load Power Factor (pf)
Inrush Current (Maximum A)
Thermal Output (Maximum kBtu/hr)
Note: Inrush currents occur only at initial application of power (very short duration for charging capacitors). No
inrush currents occur during the normal power off-on cycle.
The following table illustrates the line cord options for the Eserver pSeries 655 with their geographic,
breaker rating, and cord information.
3-Phase Supply Voltage (50/60
Hz)
Recommended
Customer-Circuit-Breaker Rating
(see Note below)
Cord Information
Recommended Receptacle
Note: The exact circuit breaker ratings may not be available in all countries. Where the specified circuit breaker
ratings are not acceptable, use the nearest available rating. Use of a time delayed circuit breaker is recommended.
Use of a GFI circuit breaker is not recommended.
88
Site and Hardware Planning Information
200 to 240
48
60
50 to 60
31.8
0.99
162
102
200-240 V
200-240 V
60 A (60-A Plug)
60 A (60-A Plug)
or
100 A (100-A Plug)
6 and 14 foot, 6
14 foot, 6 AWG
AWG line cord
line cord,
(60-A Plug)
(electrician
or
installed)
6 and 14 foot, 6
AWG line cord
(100-A Plug)
IEC309, 60 A, type
Not specified,
460R9W (not
electrician installed
provided)
or
IEC309, 100A,
type 4100R9W
(not provided)
380 to 415
32
50 to 60
31.8
0.97
162
102
380-415 V
30 A
14 foot, 8 AWG
6 and 14 foot, 10
line cord,
AWG line cord
(electrician
installed)
Not specified,
IEC309, 30 A, type
electrician installed
430R7W (not
480
24
50 to 60
31.8
0.95
162
102
480 V
25 A
provided)