7013 Model J50 - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

7013 Model J50

Dimensions
Height
Width
Depth
Weight
Minimum
Maximum
Electrical
Power source loading
(typical in kVA)
Voltage range (V ac)
Frequency (hertz)
Thermal output
(typical)
Power requirements
(typical)
Power factor
Inrush current
Maximum altitude
Temperature
Requirements
Humidity
Requirements
(Noncondensing)
Without tape drive
With tape drive
Wet Bulb
Requirements
1,4
Noise Emissions
L
WAd
L
pAm
<L
>
pA
m
Impulsive or
prominent discrete
tones
Clearances
Install/Air Flow²
Service
2
Footprint
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
2. The amount of space needed by the unit during normal operation is indicated by the footprint dimensions.
3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
4. The values for <L
>
pA
m
100 to 125 or 200 to 240 (autoranging)
35 amps at 120 V ac, 70 amps at 240 V ac
Operating
10 to 32°C
(50 to 90°F)
Operating
8 to 80%
20 to 80%
23°C (73°F)
Operating
5.8 bels
N/A
No
Front
500mm(20 in)
500mm(20 in)
500mm(20 in)
Width
1630mm(64 in)
not available at the time of publishing.
610 mm
24 in.
360 mm
14.2 in.
750 mm
29.5 in.
67 kg
148 lbs.
84 kg
185 lbs.
0.6
50 or 60
1843 Btu/hr
540 watts
0.8 to 1.0
2500 m (8202 ft.)
Non-Operating (Power Off)
Non-Operating (Power Off)
Back
500mm(20 in)
N/A
Chapter 2. Physical Characteristics of Systems
10 to 43°C
50 to 109°F)
8 to 80%
8 to 80%
27°C (80°F)
Idle
5.5 bels
N/A
No
Left
Right
500mm(20 in)
N/A
N/A
Depth
1750mm(70 in)
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7006 42tEserver pseries7006 42w7007 powerportable n407008 powerstation m207008 powerstation m2a ... Show all