2104 Model Du3 Expandable Storage Plus - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

2104 Model DU3 Expandable Storage Plus

Dimensions
Height
Width
Depth
Weight¹
Minimum
Maximum
Electrical (For each drawer)
Power source loading
Voltage range (V ac)
Frequency (hertz)
Thermal output (Maximum)
Power Requirements (Maximum)
Power factor
Inrush current
Maximum altitude
Temperature Requirements²
Humidity Requirements
(Noncondensing)
Wet Bulb
Noise Emissions¹
L
WAd
L
pAm
<L
>
pA
m
Impulsive or prominent discrete tones
Clearances
Install/Air Flow²
Service
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
2. The recommended operating temperature is 22°C (72°F) or lower. At lower temperatures, the risk of failure in the
unit is reduced. If the operating temperature is above 22°C (72°F) for long periods of time, the unit will be
exposed to a greater risk of failure from external causes.
128 mm
447 mm
563 mm
22 kg
36 kg
not less than 0.95 at 50% maximum load
Operating
10 to 40°C
(50 to 104°F)
Operating
8% to 80%
27°C (80°F)
Operating
6.5 bels
N/A
N/A
N/A
Front
Back
1140 mm(45 in)
810 mm (32 in)
1140 mm(45 in)
810 mm (32 in)
Chapter 5. Physical Characteristics of the 2100 Series
5 in.
(3 EIA units)
17.6 in.
22.2 in.
49 lbs.
80 lbs.
N/A
100 to 240
50 to 60
1126 Btu/hr
330 watts
40 amps
2133 m (7000 ft.)
Non-Operating
10 to 52°C
(50 to 125°F)
Non-Operating
8% to 80%
27°C (80°F)
6.1 bels
Left
N/A
When mounted in
a rack
Idle
N/A
N/A
N/A
Right
N/A
235

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7006 42tEserver pseries7006 42w7007 powerportable n407008 powerstation m207008 powerstation m2a ... Show all