2104 Model Tl1 Expandable Storage Plus - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

2104 Model TL1 Expandable Storage Plus

Dimensions
Height
Width (at pedestal)
Depth
Weight
Minimum
Maximum
Electrical
Power source loading
Power factor
Voltage range (V ac)
Frequency (hertz)
Thermal output
(Maximum)
Maximum altitude
Temperature
Requirements
(See note)
Humidity
Requirements
(Noncondensing)
Wet Bulb
Noise Emissions¹
L
WAd
L
pAm
<L
>
pA
m
Impulsive or
prominent discrete
tones
Clearances
Install/Air Flow²
Service
2
Footprint
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
2. The amount of space needed by the unit during normal operation is indicated by the footprint dimensions.
Note: The recommended operating temperature is 22°C (72°F) or lower. At lower temperatures, the risk of failure in
the unit is reduced. If the operating temperature is above 22°C (72°F) for long periods of time, the unit will be
exposed to a greater risk of failure from external causes.
236
Site and Hardware Planning Information
not less than 0.97 at 25% of maximum load
Operating
10 to 40°C
(50 to 104°F)
Operating
8 to 80%
27°C (80°F)
Operating
6.6 bels
N/A
N/A
N/A
Front
152 mm(6 in)
152 mm(6 in)
1000 mm(39 in)
1000 mm(39 in)
Width
281mm(11 in)
529 mm
21.0 in.
281 mm
11.0 in.
594 mm
23.5 in.
43.5 kg
96 lbs.
54.5 kg
120 lbs.
N/A
88 to 264
50 or 60
921 Btu/hr
2133 m (7000 ft.)
Back
1000 mm(39 in)
Non-Operating
10 to 52°C
(50 to 125°F)
Non-Operating
8 to 80%
27°C (80°F)
Idle
6.5 bels
N/A
N/A
No
Left
Right
N/A
N/A
1000 mm(39 in)
Depth
898mm(35.5 in)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7006 42tEserver pseries7006 42w7007 powerportable n407008 powerstation m207008 powerstation m2a ... Show all