7015 Models R10, R20, And R21 Cpu Drawers - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

7015 Models R10, R20, and R21 CPU Drawers

Dimensions
Height
Width
Depth
Weight
Minimum
(Configuration
dependant)
Electrical
Power source loading
(typical in kVA)
Voltage range (V ac)
Frequency (hertz)
Thermal output
(typical)
Power requirements
(typical)
Power factor
Inrush current³
Maximum altitude
Temperature
Requirements
Humidity
(Noncondensing)
Without tape drive
With tape drive
Wet Bulb
Requirements
Without tape drive
With tape drive
1,2
Noise Emissions
L
WAd
L
pAm
<L
>
pA
m
Impulsive or
prominent discrete
tones
Clearances
Install/Air Flow
Maintenance of a proper service clearance should allow proper air flow.
Service
(See service clearances for the R00 System Rack)
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
2. Noise emissions data for Models R10 and R20 CPU Drawers are based on a processor drawer mounted in a
R00 System Rack.
3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
266.7 mm
445.5 mm
610.0 mm
30.3 kg
Operating
10 to 40°C
(50 to 104°F)
Operating
8 to 80%
20 to 80%
27°C (80°F)
23°C (73°F)
Operating
6.4 bels
N/A
49 dBA
No
Front
Back
10.5 in.
17.5 in.
24.0 in.
65 lbs.
0.29KVA
200 to 240
50 or 60
850 Btu/hr
250 watts ( Model R10)
280 watts (Model R20)
0.85 min
20 amps
2135 m (7000 ft.)
Left
Chapter 2. Physical Characteristics of Systems
Non-Operating
10 to 40°C
(50 to 104°F)
Non-Operating
8 to 80%
20 to 80%
27°C (80°F)
27°C (80°F)
Idle
6.2 bels
N/A
47 dBA
No
Right
43

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7006 42tEserver pseries7006 42w7007 powerportable n407008 powerstation m207008 powerstation m2a ... Show all

Table of Contents