7028 Models 6C4 And 6E4 - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

7028 Models 6C4 and 6E4

The Model 6C4 is a rack-mounted server system and the Model 6E4 is a deskside tower system.
Dimensions
Height
Width
Depth
Weight
Minimum configuration
Maximum configuration
Electrical
Power source loading (typical in kVA)
Power source loading (max. in kVA)
Voltage range (V ac)
Frequency (hertz)
Voltage range (V dc)
Thermal output (typical)
Thermal output (max.)
Power requirements (typical)
Power requirements (max.)
Power factor - US, World Trade, Japan
Inrush current²
Maximum altitude³,⁴
Temperature Requirements³
Humidity Requirements⁴
(Noncondensing)
Wet Bulb
Model 6C4 Noise Emissions
L
WAd
<L
>
pA
m
Model 6E4 Noise Emissions
L
WAd
<L
>
pA
m
Install/Air Flow
Service
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions. See noise emissions note
4.
2. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
3. The upper limit of the dry bulb temperature must be derated 1°C per 137 m (450 ft.) above 915 m (3000 ft.).
4. The upper limit of the wet bulb temperature must be derated 1°C per 274 m (900 ft. ) above 305 m (1000 ft.).
5. Levels are for a single system installed in a T00 32 EIA rack with the center of the unit approximately 1500 mm
(59 in.) off the floor.
6. Levels apply to the following hardware configuration: 2 way 1 gigahertz processor, 3 Hard files, 2048 gigabytes of
RAM, Redundant system (Two 645 watt power supply, 2 processor fans).
7. Levels apply to the following hardware configuration: 2 way 1 gigahertz processor, 2 Hard files, 2048 gigabytes of
RAM, Non-redundant system (One 645 watt power supply, 1 processor fan).
8. All measurements made in accordance with ISO 7779 , and declared in conformance with ISO 9296.
82
Site and Hardware Planning Information
Rack (Model 6C4)
172.8 mm (6.8 in)
4EIA Units
444 mm (17.5 in.)
609.6 mm (24.0 in.)
1-way, 2-way processors: 0.348, 4-way processor: 0.522
1-way, 2-way processors: 0.522, 4-way processor: 0.783
1-way, 2-way processors: 1129 Btu/hr, 4-way processor: 1693 Btu/hr
1-way, 2-way processors: 1693 Btu/hr, 4-way processor: 2540 Btu/hr
1-way, 2-way processors: 330 watts, 4-way processor: 500 watts
1-way, 2-way processors: 500 watts, 4-way processor: 750 watts
Operating
5 to 35°C
41 to 95°F)
Operating
8 to 80%
27°C (80°F)
Operating
1, 5, 6
Operating
1, 7
Maintenance of service clearance will allow proper air flow.
See service clearances for the 7014 T00 Rack
32 kg (70.4 lbs.)
47.3 kg (104.8 lbs.)
100 to 127 or 200 to 240 (autoranging)
50 / 60
Not supported
0.96
50 amps
2135 m (7000 ft.)
6.1 bels
44 dBA
6.0 bels
42 dBA
Tower (Model 6E4)
530 mm (20.9 in.)
300 mm (11.8 in.)
725 mm (28.5 in.)
Non-Operating
10 to 52°C
(50 to 126°F)
Non-Operating
8 to 80%
27°C (80°F)
Idle
6.0 bels
43 dBA
Idle
5.9 bels
41 dBA