7017 Model S85 - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

7017 Model S85

The S85 can be used with a T00 or T42 style I/O rack. See "Model T00 Rack" on page 31. The rack can
be ordered by feature code with your system.
Dimensions
Height
Width
Depth
Weight
Minimum (Configuration dependant)
Electrical
Power source loading
(maximum in kVA)
Voltage range (V ac)
Frequency (hertz)
Thermal output (Maximum)
Power requirements (Maximum)
Power factor
Inrush current³
Maximum altitude
Temperature Requirements
Humidity
Noncondensing
Wet Bulb Requirements⁶
1,2
Noise Emissions
L
WAd
L
pAm
<L
>
pA
m
Impulsive or prominent discrete tones
Clearances
Install/Air Flow
Service
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
2. Noise emissions data for Model S85 are based on a system with the doors closed.
3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
4. The use of the PCI SSA Multi-Initiater/RAID EL in the Model S80 and S85 I/O Drawer 10 EIA limits the system
usage to a 28°C (82°F) environment maximum.
5. The upper limit of the dry bulb temperature must be derated 1 degree C per 137M (450 ft.) above 1295M (4250
ft.)
6. The upper limit of the wet bulb temperature must be derated 1 degree C per 274M (882 ft.) elevation above
1370M (4500 ft.)
7. For systems with FC 6120: 80/160 GB Internal Tape Drive with VXA Technology or FC 6134: 60/150 GB 16-bit
8mm Internal Tape Drive, the maximum operating temperature is limited. For additional information about this
limitation, refer to the following table.
4,5
Operating⁷
10 to 38°C
(50 to 100°F)
Operating
23°C (73°F)
Operating
Front
Maintenance of a proper service clearance should allow proper air flow.
See "Service Clearances for S80 or S85 System With T00 Style I/O Rack"
on page 36.
1577 mm
565 mm
1200 mm
400 kg
2.129KVA
200 to 240
50 - 60
6904 Btu/hr
2023 watts
0.92 to 0.98
43 amps
2135 m (7000 ft.)
8 to 80%
6.9 bels
N/A
49.5 dBA
None
Back
Chapter 2. Physical Characteristics of Systems
62.0 in.
22.2 in.
47.2 in.
880 lbs.
Non-Operating
1 1 to 60°C
(34 to 140°F)
Non-Operating
8 to 80%
23°C (73°F)
Idle
6.8 bels
N/A
49.0 dBA
None
Left
Right
49

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7006 42tEserver pseries7006 42w7007 powerportable n407008 powerstation m207008 powerstation m2a ... Show all

Table of Contents