Modbus Data Tables

The data tables are shown below. The types of data are as follows: Reference data, monitor data and broadcast data.
Reference Data
The reference data table is shown below. Reference data can be read and written to.
Register No.
0000H
Reserved
Sequence Control
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
0001H
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit A
Bits B to F
0002H
Frequency reference (Set units using parameter o1-03)
0003H to 0005H
Not used
0006H
PI Setpoint
Analog output 1 setting (-11 V = 726 to 11 V = 726) → 10 V = 660
0007H
Analog output 2 setting (-11 V = 726 to 11 V = 726) → 10 V = 660
0008H
Multi-function contact output setting
Bit 0
Bit 1
Bit 2
0009H
Bits 3 to 5
Bit 6
Bit 7
Bits 8 to F
000AH to 000EH
Not used
Reference selection settings
Bit 0
Bit 1
Bits 3 to B
000FH
C
D
E
F
Note: Write 0 to all unused bits. Also, do not write data to reserved registers.
88
Table 22 Reference Data
Run Forward 1: Run 0: Stop
Run Reverse 1: Run 0: Stop
External fault1: Fault (EFO)
Fault reset1: Reset command
ComNet
ComCtrl
Multi-function digital input command 3
Multi-function digital input command 4
Multi-function digital input command 5
Multi-function digital input command 6
Multi-function digital input command 7
Not used
Digital output 1 (Terminal M1-M2) 1: ON 0: OFF
Digital output 2 (Terminal M3-M4) 1: ON 0: OFF
Not Used
Not used
Set fault contact (terminal MA-MC) output using bit 7. 1: ON 0: OFF
Fault contact (terminal MA-MC) 1: ON 0: OFF
Not used
Not used
Input PI setpoint 1: Enabled 0: Disabled
Not used
Broadcast data terminal S5 input 1: Enabled 0: Disabled
Broadcast data terminal S6 input 1: Enabled 0: Disabled
Broadcast data terminal S7 input 1: Enabled 0: Disabled
Not used