Parameter List

Parameter Name
Parameter
Modbus
Digital Operator
No.
Address
Display
A1-00
Language Selection
0100H
Select Language
A1-01
Access Level Selection
0101H
Access Level
Initialize Parameters
A1-03
0103H
Init Parameters
Password 1
A1-04
0104H
Enter Password
Password 2
A1-05
0105H
Select Password
Denotes that parameter can be changed when the drive is running. * Menu location is Pump Quick Setup when b5-01=1, and Programming when b5-01=0.
Frequency Reference
b1-01
0180H
Selection
Reference Source
Run Command Selection
b1-02
0181H
Run Source
Stopping Method
b1-03
0182H
Selection
Stopping Method
Local/Remote Run
b1-07
0186H
Selection
LOC/REM RUN Sel
Run Command Selection
b1-08
0187H
During Program
RUN CMD at PRG
Drive Delay Time Setting
b1-11
010FH
Wait to Run Time
DC Injection Braking
b2-01
0189H
Start Frequency
DCInj Start Freq
DC Injection Braking
b2-02
018AH
Current
DCInj Current
174
Table 1 Parameter List
Description
Initialization
Language selection for digital operator display.
0: English
2: Deutsch
3: Francais
4: Italiano
5: Espanol
6: Portugues
*Not returned to factory setting by initialization
This setting determines which parameters are accessible.
0: Operation Only
2: Advanced Level
Used to return all parameters to their factory or user setting.
0: No Initialize
1110: User Initialize (The user must set their own parameter default
values and then parameter o2-03 must be set to "1" to save them. If the
parameter values are changed after o2-03 is set to "1," the user default
values can be restored by setting A1-03 to 1110.)
2220: 2-Wire Initial
3330: 3-Wire Initial
When the value set into A1-04 does NOT match the value set into A1-
05, parameters A1-01 thru A1-03 cannot be changed. All other
parameters as determined by A1-01 can be changed. Parameter A1-05
can be accessed by pressing the MENU key while holding the RESET
key.
Sequence
Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see
parameter H3-13)
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
Selects the run command input source.
0: Operator - "Hand" and "Off" keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
Selects the stopping method when the run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast w/Timer (A new run command is ignored if input before the
time in C1-02 expires.)
0: Cycle External RUN - If the run command is closed when switching
from hand (local) mode to auto (remote) mode, the Drive will not run.
1: Accept External RUN - If the run command is closed when
switching from hand (local) mode to auto (remote) mode, the Drive
WILL run.
Note: Used with LCD Operator only.
0: Disabled - Run command accepted only in the operation menu.
1: Enabled - Run command accepted in all menus (except when b1-02
= 0).
After a run command, Drive output will start after this delay time.
DC Braking
Sets the frequency at which DC injection braking starts when ramp to
stop (b1-03 = 0) is selected. If b2-01< E1-09, DC injection braking
starts at E1-09.
Selects the DC injection braking current as a percentage of the Drive
rated current.
Setting
Factory
Range
Setting
0 to 6
0
0 or 2
2
0 to 3330
0
0 to 9999
0
0 to 9999
0
0 to 3
0
0 to 3
0
0 to 3
0
0 or 1
0
0 or 1
0
0 to 600
0 sec
0.0 to 10.0
0.5 Hz
0 to 100
50%
YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Menu
Page
Location
No.
Programming
8
Programming
8
Programming
8
Programming
99
Programming
9
Pump Quick
10
Setup
Pump Quick
12
Setup
Programming
15
Programming
Programming
Programming
17
Programming
18
Programming
18