Download Print this page

YASKAWA iQpump Series Programming Manual page 123

Advertisement

Figure 1.96
Run
Pressure Feedback
(H3-09 = B)
Pump Fault
(H1-01 = 24)
F ault Reset
(H1-02 = 14)
Set-Point Pr eset
(H1-03 = 80)
Fixed Speed Auto
(H1-05 = 86)
Note: When the Fixed Speed Auto is activated, the sleep and lead-lag functions are disabled. This configuration is only active
in Auto Mode.
The L4-01 parameter of the last drive controls the previous drive and activates the Auto Mode (when the frequency level drops below
L4-01).
YASKAWA TM.iQp.02 iQpump Drive Programming Manual
S 1
iQ Pu m p
A 2 (4-20m A )
S 3 (H1-01)
M 1
Pump 2 Control
(H2-01 = 40)
M 1
S 4 (H1-02)
M 2
M 3
S 5 (H1-03)
M 4
S 7 (H1-05)
S N
P1-01 = 1 : Drive + 1 Pump
Run
Pressur e Feedback
(H3-09 = B )
Pump Fault
(H1-01 = 24)
Fault Reset
(H1-02 = 14)
Set-Point Preset
(H1-03 = 80)
Figure 5.28
Figure 101
S1
SN
i QP um p
A 2 (4-20mA )
S3 (H1-01)
S4 (H1-02)
S5 (H1-03)
S7 (H1-05)
Frequency Detection 2
During Run 1
(H2-01 = 5)
(H2- 2 = 0)
M 1
Digi tal
(H2-01)
O utput 1
M 2
P1-01 = 0 : Drive only
H2-01 = 5: Frequency Detection 2
H2-01 = 0 : During RUN 1
L4-01 = Must be greater than P1-06
L4-02 = 2.0 Hz
123

Hide quick links:

Advertisement

loading