Monitor List

Modbus
Parameter No.
Address
U1-01
0040H
U1-02
0041H
U1-03
0042H
U1-06
0045H
U1-07
0046H
U1-08
0047H
U1-10
0049H
U1-11
004AH
U1-12
004BH
U1-13
004CH
U1-14
004DH
U1-15
004EH
198
Table 2 Monitor List
Parameter Name Digital
Operator Display
Auto Setpoint Reference
Auto: Setpoint
Output Frequency
Output Freq
Output Current
Output Current
Output Voltage
Output Voltage
DC Bus Voltage
DC Bus Voltage
Output Power
Output kWatts
Input Terminal Status
Input Term Sts
Output Terminal Status
Output Term Sts
Drive Operation Status
Int Ctl Sts 1
Cumulative Operation Time
Elapsed Time
Software Number
FLASH ID
Terminal A1 Input Voltage
Term A1 Leve l
Auto Setpoint Reference (speed command) monitor when in auto mode, frequency reference
(speed command) setting location when in hand mode. Units changeable via P1-02.
Output frequency monitor in Hz.
Output current monitor.
Displays Drive output voltage.
Displays DC bus voltage.
Displays Drive output power.
Displays Drive input terminal status.
0
0 0 0 0 0 0 0
Output terminal ON/OFF check.
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
Displays total operating or power-on time of the Drive.
Displays Drive's software number.
Displays the input voltage on Terminal A1, as a percentage of 10 Vdc.
Description
Monitor
1: FWD. run
(Terminal S1) is ON.
1: REV. run
(Terminal S2) is ON.
1: Multi-function input 1
(Terminal S3) is ON.
1: Multi-function input 2
(Terminal S4) is ON.
1: Multi-function input 3
(Terminal S5) is ON.
1: Multi-function input 4
(Terminal S6) is ON.
1: Multi-function input 5
(Terminal S7) is ON.
1: Multi-function Contact 1
output 1 (Terminal M1-M2) is
ON.
1:Multi-function Contact 2
output 1 (Terminal M3-M4) is
ON.
Not used
Not used
1:Fault output
(Terminal MA/MB-MC) is
ON.
1: During running
1: During zero speed
1: During reverse
1: During reset signal input
1: During speed agree
1: Drive operation ready
1: During fault detection
(Minor fault)
1: During fault detection
(Major fault)