4.3

Entering the Initial Data

Quick Start Parameters
Parameter A1-01 sets the access level for the parameters. Setting it to "0000" disables access to any other
changeable parameters. Setting A1-01 to "0002", which is the factory default setting, enables access to the Quick
Start parameters, which are used to initially get the inverter and motor into operation.
The user can scroll through the Quick Start parameters using the increment key on the digital operator.
NOTE: only the settings involved in Quick Start Menu are explained here. See the programming section for other
settings for these parameters.
A1-03 Initialization
• Set to "0000" (default) for no initialization
• Set to "2220" for 2-wire initialization (terminal 1 = FWD RUN, terminal 2 = REV RUN)
• Set to "3330" for 3-wire initialization (terminal 1 = RUN, terminal 2 = STOP, terminal 3 = FWD/
REV)
• In the 2-wire and 3-wire case, all other parameters are set to the factory defaults.
A1-04 Password
• Allows entry of a password for access to masked parameters.
B1-01 Frequency Reference Source
• Set to "00" to set the speed reference from the digital operator only.
• Set to "01" (default) to set the speed reference from the inverter terminals 13 (+) and 17 (-)
B1-02 Operation Control Source
• Set to "00" to start/stop/jog the inverter from the digital operator only.
• Set to "01" (default) to start/stop/jog the inverter from the inverter control terminals.
NOTE: B1-01 and B1-02 do not have to be set to the same source; they may be set for different sources.
When B1-01 and B1-02 are set to "01", the LOCAL/REMOTE key on the operator controls the sources. LOCAL
mode allows only digital operator operation; REMOTE allows operation from control terminals or digital operator
(determined by the settings of parameter B1-01 and B1-02).
If you disconnect the digital operator, B1-01 and B1-02 must be set to something other than "00". When the power
to the inverter is cycled, these parameters will control the reference and control sources.
C1-01 Acceleration Time 1
C1-02 Deceleration Time 2
•The default time for these is 10.0 seconds. They may be changed for Quick Start, if desired.
D1-01 Preset Frequency Reference 1
D1-02 Preset Frequency Reference 2
D1-03 Preset Frequency Reference 3
D1-04 Preset Frequency Reference 4
• With the factory default settings, Presets 1 and 2 are not used.
• Preset 3 can be selected by closing input terminal 6 (factory default).
• Preset 4 can be selected by closing terminals 5 and 6 (factory default).
D1-09 Jog Frequency Reference
• The factory default is 10.0%. It may be changed if desired.
E1-01 through F1-01
• See the table on page 4 and item 19 of the VS-616PS5 QUICK START PROCEDURE on page 5.
T1-02 and T1-03
Auto Tuning Parameters
• See items 20 through 22 of the VS-616PS5 QUICK START PROCEDURE on page 5.
30
Motor Parameters
VS-616PS5 Installation & Quick Start Manual