H2 Digital Outputs
Terminal Function Selections
Parameter No.
H2-01
Terminal M1-M2 Function Selection
H2-02
Terminal M3-M4 Function Selection
Setting Range:
0 to 42
Factory Defaults: H2-01 = "40: Pump 2 Control"
H2-02 = "41: Pump 3 Control"
The iQpump drive has two multi-function outputs. By programming parameters H2-01 and H2-02, the user can assign specific functions
to each output. Below is a table with a complete list of all of the digital output functions. Because the iQpump drive is a dedicated pump
controller, the digital outputs described in this section only relate to the pump specific functions. Following the table is a more detailed
description of each of the pump related functions.
Parameter setting
0
1
2
3
4
5
6
7
8
9
A
B
C
E
F
10
Function: During Run 1 (Setting: 0)
A "During Run 1"output will close whenever the Run command is provided and the iQpump drive is outputting voltage. This will include
deceleration and DC Injection.
Function: Zero Speed (Setting: 1)
The "Zero Speed" output will close whenever the output frequency falls below the Minimum Frequency (E1-09).
Function: Fref/Fout Agree 1 (Setting: 2)
The "Fref/Fout Agree 1" output will close whenever the actual output frequency is within the Speed Agree Width (L4-02) of the current
Speed Command regardless of the direction.
YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Table 16 Digital Output Functions
Function
During Run1
Zero Speed
FREF/FOUT Agree 1
FREF/Set Agree 1
Frequency Detect 1
Frequency Detect 2
Drive Ready
DC Bus Undervoltage
Baseblock 1
Option Reference
Remote Operation
Torque Detect 1 N.O.
Loss of Reference
Fault
Terminal Not Used
Minor Fault
Parameter Name
Parameter setting
11
12
17
1A
1E
1F
20
28
39
3A
3B
3D
40
41
42
Function
Reset Cmd Active
Timer Output
Torque Detect 1 N.C.
Reverse Direction
Restart Enabled
Overload (OL1)
OH Pre-alarm
Drive Enable
Drive Waiting
Frequency Reduced, OH
Run from Serial Com
Cooling Fan Err
Pump 2 Control
Pump 3 Control
Pump Fault