o1 Monitor Configuration
o1-01 User Monitor Selection
Setting Range:
6 to 94
Factory Default: 6
Setting
6
Output Voltage (factory default)
7
DC Bus Voltage
8
Output Power
10
Input Terminal Status
11
Output Terminal Status
12
Drive Operation Status
13
Cumulative Operation Time
14
Software Number
15
Terminal A1 Input Voltage
16
Terminal A2 Input Voltage
18
Motor Secondary Current (Iq)
20
Output Frequency After Soft Start
24
PI Feedback Value
28
CPU Number
34
First Parameter Causing an OPE
36
PI Input
37
PI Output
38
PI Setpoint
39
Memobus Communication Error Code
40
Heatsink Cooling Fan Operation Time
51
Auto Mode Frequency Reference Value
52
Hand Mode Frequency Reference Value
53
PI Feedback 2 Value
90
Pump Setpoint
91
Pump Feedback
92
Pump Status
93
Total Setpoint Compensation
94
Motor Speed
o1-02 Power-On Monitor
Setting
1
Auto: Setpoint Reference (factory default)
2
Output Frequency
3
Output Current
4
User Monitor (set by o1-01)
When the iQpump drive is powered up, three monitors are displayed on the digital operator. The first and largest monitor is the "Power-
On" monitor. The factory default "Power-On monitor" is Speed Command (U1-01). Below the Speed Command monitor are the next
two sequential monitors, Output Frequency (U1-02) and Output Current (U1-03). Pressing the INCREASE key once scrolls the monitors
to show the User Monitor as selected by o1-01. The factory default for o1-01 is the Output Voltage monitor (U1-06).
The active monitor displayed when the iQpump drive is powered on can be changed to either be U1-01 (Speed Command), U1-02
(Output Frequency), U1-03 (Output Current), or the User Monitor. Whichever monitor is selected as the Power-On top monitor, the two
monitors displayed below it are the next two sequential monitors. See example below.