Parameter Name
Parameter
Modbus
Digital Operator
No.
Address
Display
Protection Fault Auto
P4-08
011CH
Restart Enable
<0032>
Prot Flt Restrt
Loss of Prime Maximum
P4-09
011DH
Restart Time After Fault
<0032>
LOP Max Rstrt T
Auto Mode Operator Run
P4-10
011EH
Power Down Storage.
AMO PwDn-Storage
Hand Mode Reference
P5-01
0124H
Source
Hand Mode Ref.
P5-02
Hand Reference
0125H
Hand Reference
P5-03
HAND/AUTO During
0114H
Run Selection
<0032>
HAND/AUTO @Run
Hand Key Function
P5-04
0513H
Selection
<0032>
Oper HAND Key
Motor Rated Power
T1-02
0702H
Mtr Rated Power
Motor Rated Current
T1-04
0704H
Rated Current
Denotes that parameter can be changed when the Drive is running.
YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Description
Setting to enable / disable Auto Restart for the following iQpump
protection faults (N = disable / Y = enable):
SP: Not Maintaining SetPoint (P1-11)
LOP: Loss of Prime (P1-12)
POC: Pump Over Cycling (P2-08))
0: POC = N LOP = N SP = N
1: POC = N LOP = N SP = Y
2: POC = N LOP = Y SP = N
3: POC = N LOP = Y SP = Y
4: POC = Y LOP = N SP = N
5: POC = Y LOP = N SP = Y
6: POC = Y LOP = Y SP = N
7: POC = Y LOP = Y SP = Y
Note: Parameter L5-01 needs to be set to "1" and program L5-03 needs
to be set to the applicable time.
If the restart fails (or is not attempted due to a continuing fault
condition) the Drive waits this many minutes before attempting another
restart.
Note: This parameter will take the place of L5-03 during a Loss of
Prime Fault restart attempt.
Stores the run status in the Auto mode when operating from digital
operator (b1-02=0).
0: Disabled.
1: Enabled.
WARNING
When the drive is powered down while running, then upon power-up it will
automatically initiate an internal run command.
Hand Mode
Sets the hand mode reference source.
0: Analog Input A1 (0-10 V).
1: Hand reference (P5-02).
Sets the frequency reference used when the hand mode is active and
P5-01 is programmed to 1.
Selects if the Drive will permit switching between HAND and AUTO
modes while running.
0: Disabled.
1: Enabled.
Switching from HAND to AUTO is not permitted when the Drive
output frequency is less than the PID minimum speed.
Switching from AUTO to HAND is not permitted when the Drive is
running in the multiplex mode with auxiliary drives enabled.
Enables or disables the "HAND" key on the digital operator.
0: Disabled.
1: Enabled.
Auto-Tuning
Sets the motor rated power in kW.
Note: T1-02 should be left at the default value (last 3 digits of the
Drive model number).
Sets the motor rated current. (Used only during an auto-tune.)
Setting
Factory
Menu
Range
Setting
Location
Pump Quick
0 to 7
0
Setup
0.2 to
Pump Quick
0.2 min
6000.0
Setup
Pump Quick
0 or 1
0
Setup
Pump Quick
0 or 1
1
Setup
0.0 to
Pump Quick
0.0 Hz
120.0
Setup
0 to 1
0
Programming
0 to 1
1
Programming
0.00 to
kVA
Auto-Tuning
650.0
Dependent
kVA
kVA
Auto-Tuning
Dependent
Dependent
Page
No.
165
165
167
168
169
169
169
172
172
197