The programming of the No-Flow Activation Level (P2-11) will activate the no-flow detection function. The drive will monitor the
motor RPM and if the motor RPM falls below the No-Flow Activation Level (P2-11) and the No-Flow Detection Bandwidth (P2-13), the
no-flow process is activated.
The drive will check for system response by monitoring the motor RPM for a time specified by the No-Flow Detection Time (P2-13). If
the motor RPM is within the bandwidth programmed in P2-12 after the time specified by P2-13, the setpoint will be lower by the value
programmed in the No-Flow Setpoint Compensation (P2-16). The drive will wait for the system to stabilize for the time programmed in
the No-Flow Stabilization Time (P2-14).
After the time programmed in P2-14 has elapsed, the setpoint is returned to the original value. The drive will again wait for the system to
stabilize for the time programmed in P2-13. If the time programmed in P2-13 has elapsed, the drive will continue to monitor the feedback
level. If the feedback level falls within the No-Flow Delta Feedback Level (P2-15) for a time programmed in No-Flow Feedback Delay
Time (P2-17), the drive will enter a "sleep" mode after the P2-13 time elapses.
Figure 1.104
Fmax
0 Hz
No-flow detection is active below P2-11 Level
P2-11
No-Flow
Activation
Level
0 RPM
Set-Point
Set-Point
YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Output Frequency
Motor RPM
Monitor Motor RPM
1
P2-13 No-Flow
Detection Time
2
Feedback Signal
Auto Mode Run
Figure 109
Decrease Set-Point
4
by P2-16 Setting
Increase Set-Point by
P2-16 Setting
Set-Point – P2-16
P2-14 No-Flow
Stabilize Time
3
P2-17 No Flow
P2-13 No-Flow
Feedback Delay Time
5
TIME
Note: Sleep function P2-02 is disable (P2-02 = 0)
P2-12 No-Flow Detection
Bandwidth
6
P2-15 No-Flow Delta
Feedback Level
No-Flow Detected
137