Function: 3-Wire Control (Setting: 0)
When one of the digital inputs is programmed for 3-Wire control, that input becomes a Forward/Reverse directional input. Whenever the
input is open, the iQpump drive will be set for forward rotation of the motor shaft. If the input it closed, then the motor shaft will rotate in
the reverse direction whenever a there is a Run input. The S1 and S2 digital inputs will function as a Run and Stop input respectively.
Figure 1.32
Figure 1.33
Forward/reverse
command
Important: As long as the S1(Run Command) input is applied in for at least 50 ms the Run command will latch internally in the Drive.
Function: Local/Remote Selection (Setting: 1)
This function has been disabled. Please refer to settings "6D" and "6E".
Function: Option/Inv Selection 1 (Setting: 2)
The Option/Inv Selection function allows the user to select the source for the Run and speed commands between either the Drive's
terminals or an optional communication card. When a digital input is programmed for the Option/Inv Selection function (H1-0x = 2) that
input will function as follows:
Option/Inv Selection Input Status
To switch the command source between the option card and the terminals be sure to program the following parameters:
• Set b1-01 (Auto Setpoint Reference Selection) to 1 (Terminals).
• Set b1-02 (Run Command Selection) to 1 (Terminals).
• Set H1-0x (Input Terminal Function Selection) to 2.
Important: Switching between the different Reference and Run sources can only be done while the iQpump drive is stopped.
48
Stop switch
Operation switch
(NC contact)
(NO contact)
3-wire control
Figure 32 Terminal Configuration for 3-Wire Control
Run command
Stop command
OFF (forward)
Motor speed
Stop
Figure 33 3-Wire Control Timing Diagram
Table 9 Digital Input Functions
CLOSED
OPEN
Run command
(run on momentary close)
Stop command
(stop on momentary open)
SN
Sequence input common
50 ms min.
Can be either ON or OFF
ON (reverse)
Forward
Reverse
Run and Speed Command Source
From the control circuit and analog input terminals
From the Communications Option Card
OFF
(stopped)
TIME
Stop
Forward
YASKAWA TM.iQp.02 iQpump Drive Programming Manual