Download Print this page

YASKAWA iQpump Series Programming Manual page 90

Advertisement

Register No.
Sequence input status
Bit 0
Bit 1
Bit 2
002BH
Bit 3
Bit 4
Bit 5
Bit 6
Bits 7 to F
Drive status
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
002CH
Bit 7
Bit 8
Bit 9
Bit A
Bit B
Bit C
Bit D
Bit E
Bit F
Multi-function digital output status
Bit 0
002DH
Bit 1
Bit 2
Bits 3 to F
002EH - 0030H
Not used
0031H
Main circuit DC voltage
0032H - 0037H
Not used
0038H
PI feedback level (Input equivalent to 100%/Max. output frequency; 10/1%; without sign)
0039H
PI input level (±100%/±Max. output frequency; 10/1%; with sign)
003AH
PI output level (±100%/±Max. output frequency; 10/1%; with sign)
003BH
CPU software number
003CH
Flash software number
Communication error details
Bit 0
Bit 1
Bit 2
003DH
Bit 3
Bit 4
Bit 5
Bit 6
Bits 7 to F
003EH
kVA setting
003FH
Control method
Note: Communication error details are stored until an error reset is input (errors can be reset while the Drive is operating).
90
Input terminal S1 1: ON 0: OFF
Input terminal S2 1: ON 0: OFF
Multi-function digital input terminal S3 1: ON 0: OFF
Multi-function digital input terminal S4 1: ON 0: OFF
Multi-function digital input terminal S5 1: ON 0: OFF
Multi-function digital input terminal S6 1: ON 0: OFF
Multi-function digital input terminal S7 1: ON 0: OFF
Not used
Operation1: Operating
Zero speed1: Zero speed
Frequency agree1: Matched
Desired frequency agree1: Matched
Frequency detection 11: Output frequency £ L4-01
Frequency detection 21: Output frequency Š L4-01
Drive startup completed1: Startup completed
Low voltage detection 1: Detected
Baseblock1: Drive output baseblock
Frequency reference mode1: Not communication 0: Communication
Run command mode1: Not communication 0: Communication
Overtorque detection1: Detected
Frequency reference lost1: Lost
Retrying error1: Retrying
Error (including Modbus communications time-out) 1:Error occurred
Modbus communications time-out 1: Timed out
Multi-function digital output 1 (terminal M1-M2) 1: ON 0: OFF
Multi-function digital output 2 (terminal M3-M4): 1: ON 0: OFF
Not used
Not used
CRC error
Invalid data length
Not used
Parity error
Overrun error
Framing error
Time-out
Not used