H3-10 Terminal A2 Gain Setting
Setting Range:
0.0 to 1000.0%
Factory Default: 100.0%
H3-11 Terminal A2 Bias Setting
Setting Range:
-100.0% to +100.0%
Factory Default: 0.0%
Parameters H3-10 and H3-11 perform the same function for the A2 analog input that parameters H3-02 and H3-03 perform for the A1
analog input. Please refer to the parameter description for H3-02 and H3-03 for information about H3-10 and H3-11.
These parameters could be used for final calibration of a factory or field installed pressure to electric transducer input connected to
terminal A2 and AC. This field calibration may be needed if there is a job site variation from the typical 3 to 15 PSIG pneumatic signal
input range.
H3-12 Analog Input Filter Time Constant
Setting Range:
0.00 to 2.00 sec
Factory Default: 0.30 sec
An analog input filter can be used to prevent erratic iQpump drive control when a "noisy" analog reference is used. Parameter H3-12 sets
the time constant for a first order filter that will be applied to both the A1 and A2 analog inputs. The iQpump drive operation becomes
more stable the longer the time programmed, but it becomes less responsive to rapidly changing analog signals.
Figure 1.72
H3-13 Master Frequency Reference Terminal Selection
Setting
0
Main Fref = A1 (factory default)
1
Main Fref = A2
Parameter H3-13 allows the programmer to select which analog input will serve as the Speed Command input when "Terminals" are
selected as the Auto Mode Speed source (b1-01 = "1: Terminals"), or Terminal is selected as the reference source for the Hand mode (b1-
12 = "1: Terminals"). For the A2 analog input to be an effective selection for the H3-13 parameter, parameter H3-09 must be configured
as Aux Reference (H3-09 = "2: Aux Reference").
If H3-09≠2, then the A1 analog input will be used regardless of the setting of parameter b1-12.
76
input
Noisy
signal
Figure 72 Analog Input Filter Time Constant Effect on "Noisy" Signal
Analog
Input
Filter
Internal Analog Input Valve
Description
Analog
(Filtered)
input post
YASKAWA TM.iQp.02 iQpump Drive Programming Manual