H4 Analog Outputs
H4-01 Terminal FM Monitor Selection
Setting Range:
1 to 53
Factory Default: 2: Output Freq
The FM and AM analog output terminals can be programmed to output a 0-10 Vdc signal proportional to any one of functions detailed in
Table 18 on page
77.
Setting
1
2
3
6
7
8
15
16
18
* SFS is the internal soft starter signal. This signal is generated from the reference and often it passes through the accel/ decel functions.
When the H4-01 or H4-04 are configured the iQpump drive will output 10 Vdc to represent 100% of the function programmed into them.
Figure 1.73
Figure 73 Analog Output Signal Level as a Function of the Monitor Value
Function: Frequency Ref (Setting: 1)
The analog output level will correspond to the chosen Speed Command input whether it is input via the digital operator, analog input, or
serial communication. 100% will be equivalent to the maximum output frequency of the iQpump drive (E1-04).
Function: Output Freq (Setting: 2)
The analog output level will correspond to the actual Speed being output by the iQpump drive and will include the acceleration and
deceleration ramps. 100% will be equivalent to the maximum output frequency of the iQpump drive (E1-04).
Function: Output Current (Setting: 3)
The analog output level will correspond to the output current level of the Drive. 100% will be equivalent to the Drives rated output
current which is based on the kVA Rating of the iQpump drive (o2-04).
Function: Output Voltage (Setting: 6)
The analog output level will correspond to the output voltage level of the Drive. 100% will be equivalent to either 200 Vac or 400 Vac
depending on the input voltage rating of the Drive.
Function: DC Bus Voltage (Setting: 7)
The analog output level will correspond to the voltage level of the Drive's DC Bus. 100% will correspond to 400 Vdc for the 240 Vac
input iQpump drive and 800 Vdc for the 480 Vac input Drive.
YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Table 18
Description
Frequency Ref
Output Freq
Output Current
Output Voltage
DC Bus Voltage
Output kWatts
Term A1 Level
Term A2 Level
Mot SEC Current
10 V
0
Setting
20
24
31
36
37
38
51
52
53
100%
Monitor
Function Level
Description
SFS Output*
PI Feedback
Not Used
PI Input
PI Output
PI Setpoint
Auto Mode Fref
Hand Mode Fref
PI Feedback 2
77