YASKAWA iQpump Series Programming Manual page 96

Advertisement

L1 Motor Overload
L1-01 Motor Overload Protection Selection
Setting
0
Disabled
1
Std Fan Cooled (Enabled) ( factory default )
The iQpump drive has an I
2
iQpump drive bases the protection on time, output current, and output frequency. The electronic thermal overload function is UL-
recognized so an external thermal overload relay is not required.
If the iQpump drive is connected to a single motor, the motor overload protection should be enabled (L1-01 = "1: Std Fan Cooled")
unless another means of preventing motor thermal overload is provided.
The time before the OL1 fault will occur changes as the output frequency is reduced. The maximum output current level at which there is
no time limit for operation (the OL Start Point) is different depending on the output frequency. For instance, if the iQpump drive is being
operated at 60 Hz and the output current level is below 106% of the motor's rated current (E2-01), the iQpump drive will run without an
OL1 fault indefinitely. Once the 106% output current level is exceeded, de-rating of the OL1 time starts.
Figure 1.81
Important: If the iQpump drive is connected to more than one motor for simultaneous operation, the electronic overload protection
should be disabled (L1-01 = "0: Disabled") and each motor should be wired with its own motor thermal overload.
L1-02 Motor Overload Protection Time
Setting Range:
0.1 to 20.0 Minutes
Factory Default: 8.0 Minutes
The L1-02 parameter will set the allowed operation time before the OL1 fault will occur when the iQpump drive is running at 60 Hz and
133% of the motor's full load amp rating (E2-01). Adjusting the value of L1-02 can shift the set of OL1 curves up the Y-axis of the
diagram below but will not change the shape of the curves.
96
t electronic overload protection function, the OL1 fault, for protecting the motor from overheating. The
106%
88%
67%
0
Figure 86 Motor Overload Protection Curve
Description
Continuous Operation Area
60
20
Output Frequency
(Hz)
YASKAWA TM.iQp.02 iQpump Drive Programming Manual