YASKAWA iQpump Series Programming Manual page 194

Advertisement

Parameter Name
Parameter
Modbus
Digital Operator
No.
Address
Display
Drive Multi/Maximum
P3-02
0615H
Level
Max-Multi Level
P3-03
Add Pump Delta Level
0616H
Add Pump D-Lvl
P3-04
Add Pump Delay Time
0617H
Add Pump Dly Tm
Shutdown Pump Delta
P3-05
0618H
Level
Shdn Pump D-Lvl
Shutdown Pump Delay
P3-06
0619H
Time
Shdn Pump Dly Tm
Multi Pump Setpoint
P3-07
061AH
Increase
MP Setpoint Inc.
Multi Pump Setpoint
P3-08
061BH
Decrease
MP Setpoint Dec.
Denotes that parameter can be changed when the Drive is running.
194
Description
Sets the maximum level used for multiplex pumping operation.
Parameter is active when P3-01 = 0 or P3-01 = 2 is selected.
P3-01=0: When the output frequency rises above the level
programmed in P3-02 for a time specified in P3-04, the next available
pump will be added to the system by means of a multi-function digital
output closure (H2-XX = 40, 41).
P3-01=1: Not Used.
P3-01=2: When the output frequency rises above level programmed in
P3-02 and the delta feedback (setpoint minus feedback) has exceeded
the level programmed in P3-03 for a time specified in P3-04, the next
available pump will be added to the system by means of a multi-
function digital output closure (H2-XX = 40, 41).
Sets the level used for multiplex pumping operation. The parameter is
active when P3-01 =1 or P3-01 = 2 is selected.
P3-01=0: Not Used.
P3-01=1: When the delta feedback (setpoint minus feedback) has
exceeded the level programmed in P3-03 for a time specified in P3-04,
the next available pump will be added to the system by means of a
multi-function digital output closure. (H2-XX = 40, 41).
P3-01=2: When the output frequency rises above level programmed in
P3-02 and the delta feedback (Setpoint minus feedback) has exceeded
the level programmed in P3-03 for a time specified in P3-04, the next
available pump will be added to the system by means of a multi-
function digital output closure. (H2-XX = 40, 41).
Note: Do not program this level too close to the system setpoint or
excessive cycling of the pump system may occur.
Sets the delay time before a pump is added to the system. Works in
conjunction with parameters P3-02, P3-03, and P2-11 to P2-19.
Sets the level used for multiplex pumping operation. Parameter is
active when P3-01 = 1 or P3-01 = 2 is selected.
P3-01=0: Not Used.
P3-01=1: When the delta feedback (feedback minus setpoint) has
exceeded the level programmed in P3-05 for a time specified in P3-
06,the last pump that was brought online will be shutdown by means of
a multi-function digital output opening. (H2-XX = 40, 41).
P3-01=2: When the output frequency drops below level programmed
in P3-09 or P3-10 (depends on last pump running) and the delta
feedback (feedback minus setpoint) has exceeded the level
programmed in P3-05 for a time specified in P3-06, the last pump that
was brought online will be shutdown by means of a multi-function
digital output opening. (H2-XX = 40, 41).
Note: Do not program this level too close to the system setpoint or
excessive cycling of the pump system may occur.
Sets the delay time before one of the additional across the line pumps is
shutdown.Works in conjunction with parameters P3-02 and P3-03.
Sets the amount the Drive's setpoint will decrease for each time a new
pump is brought offline.
Pump 1: Setpoint.
Pump 1+2: Setpoint + P3-07.
Pump 1+2+3: Setpoint + (2 x P3-07).
Sets the amount the Drive's setpoint will increase for each time a new
pump is brought online.
Pump 1: Setpoint.
Pump 1+2: Setpoint - P3-08.
Pump 1+2+3: Setpoint - (2 x P3-08).
Setting
Factory
Range
Setting
0.0 to
59.0 Hz Programming
120.00
0.0 to
0.0
6000.0
(system
(system
units P1-
units P1-
02)
02)
0 to 3600
2 sec
0.0 to
0.0
6000.0
(system
(system
units P1-
units P1-
02)
02)
0 to 3600
5 sec
0.0 to
0.0
6000.0
(system
(system
units P1-
units P1-
02)
02)
0.0 to
0.0
6000.0
(system
(system
units P1-
units P1-
02)
02)
YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Menu
Page
Location
No.
149
Programming
150
Programming
150
Programming
150
Programming
151
Programming
151
Programming