Figure 1.117
Max-Multi Level
P3-02
STOP, 0Hz
System
Set-Point
Start Level
P1-04
0%
Auto Mode Run
OFF Mode
Multi-function
Output #40
Multi-function
Output #41
Wait for Start
Start System
P3-12 Delta Setpoint Feedback Acc/Dec Changeover
Setting Range:
0.0 to 6000.0
Factory Default: 0.0
The iQpump drive can be configured for multiplex pumping operation. The acceleration (Acc) and deceleration (Dec) times can be
changed when the difference between the delta setpoint and feedback are within the programmed level in the Delta Setpoint Feedback
Acc/Dec Changeover (P3-12).
The acceleration and deceleration times during this changeover are programmed into C1-05 and C1-06, respectively.
This function is used to improve the pump regulation.
Setting P2-12 to a value of 0 will disable this function.
YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Multiplex Stabilize Time
Add Pump Delay Time P3-04
Output Frequency
Start Level Delay
P1-05
AUTO MODE RUN:
PUMP 1
START DELAY
Multiplex Stabilize Time
P3-11
Add Pump Delay Time
P3-04
ADD PUMP 2
Start System, Incoming Run Command
TIME
Figure 122
Lead/Lag Functions
P3-11
Disabled until
stabilization timer
expires
Feedback
ADD PUMP 3
155