Figure 1.111
Output #41
Output #40
Figure 116
Auxiliary Pump De-Staging (OFF)
The de-staging of the auxiliary pumps 2 and 3 will occur in the reverse order of the staging process described previously.
The de-staging of auxiliary pump 3 occurs when the difference between the system's feedback level minus the setpoint exceeds the value
programmed in the Shutdown Pump Delta Level (P3-05) for the time programmed in the Add Pump Delay Time (P3-04).
The de-staging of auxiliary pump 2 occurs when the auxiliary pump 3 is de-staged and the difference between the system's feedback
level and setpoint exceeds the value programmed in the Shutdown Pump Delta Level (P3-05) for the time programmed in Add Pump
Delay Time (P3-04). Refer to
Figure 117
for the de-staging of the auxiliary pumps 2 and 3 using the "feedback level" control method.
146
YASKAWA TM.iQp.02 iQpump Drive Programming Manual