YASKAWA iQpump Series Programming Manual page 177

Advertisement

Parameter Name
Parameter
Modbus
Digital Operator
No.
Address
Display
Accel/Decel Switch
C1-11
020AH
Frequency
Acc/Dec SW Freq
S-Curve Characteristic at
C2-01
020BH
Accel Start
SCrv Acc @ Star t
S-Curve Characteristic at
C2-02
020CH
Accel End
SCrv Acc @ End
Torque Compensation
C4-01
0215H
Gain
Torq Comp Gain
Torque Compensation
C4-02
0216H
Primary Delay Time
Torq Comp Time
Denotes that parameter can be changed when the drive is running.
Normal Duty Selection
C6-01
0223H
Normal Duty Sel
Carrier Frequency
C6-02
0224H
Selection
CarrierFreq Sel
Carrier Frequency Upper
C6-03
0225H
Limit
CarrierFreq Max
Carrier Frequency Lower
C6-04
0226H
Limit
CarrierFreq Min
Carrier Frequency
C6-05
0227H
Proportional Gain
CarrierFreq Gain
YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Description
Sets the frequency for automatic switching of accel / decel times.
Fout < C1-11: Accel/Decel Time 2
Fout >= C1-11: Accel/Decel Time 1
Multi-function input "Multi-Acc/Dec 1" has priority over C1-11.
S-Curve Acc/Dec
S-curve is used to further soften the starting ramp.
The longer the S-curve time, the softer the starting
ramp.
Run
command
ON
Output frequency
C2-02
C2-01
Torque Comp
This parameter helps to produce better starting torque. It determines
the amount of torque or voltage boost based upon motor current and
motor resistance.
This parameter adjusts a filter on the output of the torque compensation
function. Increase to add torque stability, decrease to improve torque
response.
Carrier Freq
1: Normal Duty 1
2: Normal Duty 2
Carrier frequency sets the number of pulses per second of the output
voltage waveform.
0: Low Noise (Carrier frequency is randomly moduled for lower
audible noise)
1: Fc = 2.0 kHz
2: Fc = 5.0 kHz
3: Fc = 8.0 kHz
4: Fc = 10.0 kHz
5: Fc = 12.5 kHz
6: Fc = 15.0 kHz
F: Program (Determined by the settings of C6-03 thru C6-05)
Maximum carrier frequency allowed when C6-02 = F.
Minimum carrier frequency allowed when C6-02 = F.
Sets the relationship of output frequency to carrier frequency when C6-
02 = F.
Setting
Range
0.0 to
200.0
0.00 to
2.50
OFF
0.00 to
2.50
Time
0.00 to
2.50
0 to 10000
1 or 2
0 to F
0.4 to 15.0
kHz
0.4 to 15.0
kHz
0 to 99
Factory
Menu
Page
Setting
Location
No.
0.0 Hz
Programming
30
0.20 sec Programming
32
0.20 sec Programming
32
1.00
Programming
33
200 ms
Programming
33
2
Programming
34
kVA
Programming
34
Dependent
kVA
Programming
34
Dependent
kVA
Programming
34
Dependent
0
Programming
34
177