Parameter Name
Parameter
Modbus
Digital Operator
No.
Address
Display
b5-07
PI Offset Adjustment
01ABH
PI Offset
PI Primary Delay Time
b5-08
01ACH
Constant
PI Delay Tim e
PI Output Level
b5-09
01ADH
Selection
Output Level Sel
PI Output Gain Setting
b5-10
01AEH
Output Gain
PI Feedback Reference
Missing Detection
b5-12
01B0H
Selection
PFb los Det Sel
PI Feedback Loss
b5-13
01B1H
Detection Level
Fb los Det Lvl
PI Feedback Loss
b5-14
01B2H
Detection Time
Fb los Det Time
PI Accel/Decel Time
b5-17
01B5H
Acc/Dec Time
Denotes that parameter can be changed when the drive is running.
Energy Saving Control
b8-01
01CCH
Selection
Energy Save Sel
Energy Saving
b8-04
01CFH
Coefficient Value
Energy Save COEF
Power Detection Filter
b8-05
01D0H
Time
kW Filter Time
Search Operation Voltage
b8-06
01D1H
Limit
Search V Limit
C1-01
Acceleration Time 1
0200H
Accel Time 1
C1-02
Deceleration Time 1
0201H
Decel Time 1
C1-03
Acceleration Time 2
0202H
Accel Time 2
C1-04
Deceleration Time 2
0203H
Decel Time 2
C1-05
Acceleration Time 3
0204H
Accel Time 3
C1-06
Deceleration Time 3
0205H
Decel Time 3
Fast Stop Time
C1-09
0208H
Fast Stop Time
Denotes that parameter can be changed when the drive is running.
176
Description
Sets the amount of offset of the output of the PI controller. Set as a% of
fmax.
The PI Offset Adjustment parameter has two different uses. Parameter
b5-07 serves different functions depending on whether it is used on a
standard PI loop or a Differential PI loop.
1: Parameter b5-07 causes an offset to be applied to the output of the PI
function in a non-Differential PI loop. Every time the PI output is
updated, the offset is summed with the PI output. This can be used to
artificially kick-start a slow starting PI loop.
2: If the Drive is configured for Differential PI Regulation (H3-09=16),
then the PI Offset is the targeted maintained differential between the
signal measured on analog input A1 and the signal measured on analog
input A2.
Sets the amount of time for a filter on the output of the PI controller.
Determines whether the PI controller will be direct or reverse acting.
0: Normal Output (direct acting)
1: Reverse Output (reverse acting)
Sets the output gain of the PI controller.
0: Disabled
1: Alarm
2: Fault
Sets the PI feedback loss detection level as a percentage of maximum
frequency (E1-04).
Sets the PI feedback loss detection delay time in terms of seconds.
Applies an accel/decel time to the PI setpoint reference.
Energy Saving
Energy Savings function enable/disable selection
0: Disabled
1: Enabled
Used to fine-tune the energy savings function.
Accel / Decel
Sets the time to accelerate from zero to maximum frequency.
Sets the time to decelerate from maximum frequency to zero.
Sets the time to accelerate from zero to maximum frequency when
selected via a multi-function input.
Sets the time to decelerate from maximum frequency to zero when
selected via a multi-function input.
Sets the time to accelerate from zero to maximum frequency when
activated by P3-12. Used for system response stabilization.
Sets the time to decelerate from maximum frequency to zero when
activated by P3-12. Used for system response stabilization.
Sets the time to decelerate from maximum frequency to zero for the
"Fast Stop" function.
Setting
Factory
Range
Setting
–100.0 to
0.0%
+100.0
0.00 to
0.00 sec Programming
10.00
0 or 1
0
0.0 to 25.0
1.0
0 to 2
0
0 to 100
0%
0.0 to 25.5
1.0 sec
0.0 to 25.5
0.0 sec
0 or 1
0
0.0 to
kVA
655.00
Dependent
0 to 2000
20 ms
0 to 100
0%
25.0 sec
25.0 sec
10.0 sec Programming
0.0 to
6000.0
10.0 sec Programming
50.0 sec Programming
50.0 sec Programming
0.0 to
10.0 sec Programming
6000.0
YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Menu
Page
Location
No.
Programming
26
26
Programming
27
Programming
27
Pump Quick
Setup
Pump Quick
27
Setup
Pump Quick
27
Setup
Programming
28
Programming
29
Programming
29
Programming
29
Programming
29
Pump Quick
30
Setup
Pump Quick
30
Setup
30
30
30
30
30