Monitor Data
The following table shows the monitor data. Monitor data can only be read.
Register No.
Drive status
Bit 0
Bit 1
Bit 2
Bit 3
0020H
Bit 4
Bit 5
Bit 6
Bit 7
Bits 8 to F
Fault details
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
0021H
Bit 7
Bit 8
Bit 9
Bit A
Bit B
Bit C
Bit D
Bit E
Bit F
Data link status
Bit 0
Bit 1
0022H
Bit 2
Bit 3
Bit 4
Bits 5 to F
Frequency
0023H
reference
Output
0024H
frequency
Output voltage
0025H
reference
0026H
Output current
0027H
Output power
0028H
Torque reference U1-09
0029H
Not used
002AH
Not used
YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Table 23 Monitor Data
Running 1: Running 0: Stopped
Reverse operation 1: Reverse operation 0: Forward operation
Drive startup complete 1: Completed 0: Not completed
Fault1: Fault
Data setting error1: Error
Multi-function digital output 1 (terminal M1 - M2) 1: ON 0: OFF
Multi-function digital output 2 (terminal M3 - M4) 1: ON 0: OFF
Not used
Not used
Overcurrent (OC) Ground fault (GF)
Main circuit overvoltage (OV)
Drive overload (OL2)
Drive overheat (OH1, OH2)
Not used
Fuse blown (PUF)
PI feedback reference lost (FbL)
External error (EF, EFO)
Hardware error (CPF)
Motor overload (OL1) or overtorque 1 (OL3) detected
PG broken wire detected (PGO), Overspeed (OS), Speed deviation (DEV)
Main circuit undervoltage (UV) detected
Main circuit undervoltage (UV1), control power supply error (UV2), inrush prevention circuit error (UV3), power loss
Missing output phase (LF)
Modbus communications error (CE)
Operator disconnected (OPR)
Writing data
Not used
Not used
Upper and lower limit errors
Data integrity error
Not used
U1-01
U1-02
U1-06
U1-03
U1-08
Contents