Parameter Name
Parameter
Modbus
Digital Operator
No.
Address
Display
Terminal AM Monitor
H4-04
0420H
Selection
Terminal AM Sel
Terminal AM Gain
H4-05
0421H
Setting
Terminal AM Gain
Terminal AM Bias
H4-06
0422H
Setting
Terminal AM Bias
Terminal FM Signal
H4-07
0423H
Level Selection
AO Level Select1
Terminal AM Signal
H4-08
0424H
Level Selection
AO Level Select2
Denotes that parameter can be changed when the drive is running.
Drive Node Address
H5-01
0425H
Serial Com Adr
Communication Speed
H5-02
0426H
Selection
Serial Baud Rate
Communication Parity
H5-03
0427H
Selection
Serial Com Sel
Stopping Method after
H5-04
0428H
Communication Error
Serial Fault Sel
Communication Error
H5-05
0429H
Detection Selection
Serial Flt Dtct
Drive Transmit Wait
H5-06
042AH
Time
Transmit WaitTIM
RTS Control Selection
H5-07
042BH
RTS Control Sel
YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Description
Selects which monitor will be output on terminals AM and AC.
1: Frequency Ref (100% = max. output frequency)
2: Output Freq (100% = max. output frequency)
3: Output Current (100% = Drive rated current)
6: Output Voltage (100% = 230 V or 100% = 460 V)
7: DC Bus Voltage (100% = 400 V or 100% = 800 V)
8: Output kWatts (100% = Drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100% = Motor rated secondary current)
20: SFS Output (100% = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Setpoint
Note: 100% = 10 V DC output * AM gain setting (H4-05).
Sets terminal AM output voltage (in percent of 10 V) when selected
monitor is at 100% output.
Sets terminal AM output voltage (in percent of 10 V) when selected
monitor is at 0% output.
0: 0 - 10 Vdc
2: 4-20 mA*
0: 0 - 10 Vdc
2: 4-20 mA*
* An analog output of 4 - 20 mA cannot be used with the standard
terminal board. Therefore an optional terminal board (with shunt
connector CN15) is needed.
Serial Com Setup
Selects Drive station node number (address) for terminals R+, R-, S+,
S-.*
Note: An address of "0" disables serial com.
Selects the baud rate for terminals R+, R-, S+ and S-.*
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud
Selects the communication parity for terminals R+, R-, S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity
Selects the stopping method when a communication error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a
communications fault.
1: Enabled - If communications are lost for more than the time
specified in parameter H5-09, a communications fault will occur.
Sets the time from when the Drive receives data to when the Drive
sends data.
Enables or disables "request to send" (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)
Setting
Factory
Menu
Range
Setting
Location
1 to 38
8
Programming
<0032>
0.0 to
50.0%
Programming
1000.0
–110.0 to
0.0%
Programming
110.0
0 or 2
0
Programming
0 or 2
0
Programming
0 to 20
(H5-08=0)
0 to FF
1F
Programming
(H5-08=1)
0 to 63
(H5-08=2)
0 to 4
3
Programming
0 to 2
0
Programming
0 to 3
3
Programming
0 or 1
1
Programming
5 to 65
5 ms
Programming
0 or 1
1
Programming
Page
No.
79
79
79
80
80
93
93
93
94
94
94
94
185