Download Print this page

YASKAWA iQpump Series Programming Manual page 40

Advertisement

E1 V/f Pattern
E1-01 Input Voltage Setting
Setting Ranges: 155.0 V to 255.0 V (208 V/240 V Models)
310.0 V to 510.0 V (480 V Models)
Factory Defaults: 208.0 V (208 V Models)
240.0 V (240 V Models)
480.0 V (480 V Models)
Set the Input Voltage parameter (E1-01) to the nominal voltage of the connected AC power supply. This parameter adjusts the levels of
some protective features of the iQpump drive (i.e. Overvoltage, Stall Prevention, etc.). E1-01 also serves as the Maximum/Base Voltage
used by the Preset V/Hz curves (E1-03 = 0 to D).
E1-03 V/f Pattern Selection
Setting
0
50 Hz
1
60 Hz Saturation
2
50 Hz Saturation
3
72 Hz
4
50 Hz VT1
5
50 Hz VT2
6
60 Hz VT1
7
60 Hz VT2
8
50 Hz HST1
9
50 Hz HST2
A
60 Hz HST1
B
60 Hz HST2
C
90 Hz
D
120 Hz
E
180 Hz (invalid - OPE2 fault will occur)
F
Custom V/f (factory default, with parameter values per setting 1)
FF
Custom w/o limit
The iQpump drive operates utilizing a set V/f pattern to determine the appropriate output voltage level for each commanded speed. There
are 14 different preset V/f patterns to select from with varying voltage profiles, saturation levels (frequency at which maximum voltage is
reached), and maximum frequencies.
There are also settings for Custom V/f patterns that will allow the programmer to manually set ("Customize") the V/f pattern using
parameters E1-04 through E1-13.
Using parameter E1-03, the programmer can select one of the preset V/f patterns or chose between a custom V/f pattern with an upper
voltage limit (E1-03 = "F: Custom V/f") and a custom V/f pattern without a voltage limit (E1-03 = "FF: Custom w/o limit").
40
Description
YASKAWA TM.iQp.02 iQpump Drive Programming Manual

Hide quick links:

Advertisement

loading