Calculation Parameters - GE Power Quality Meter Series Instruction Manual

Table of Contents

Advertisement

4 PROGRAMMING
The PQM can be programmed to calculate metering quantities and demand by various methods.
]] SETPOINTS
]] S1 PQM SETUP
] PREFERENCES
]
MESSAGE
MESSAGE
] CLOCK
]
] CALCULATION
] PARAMETERS
Figure 4–7: SETPOINTS PAGE 1 – PQM SETUP / CALCULATION PARAMETERS
EXTRACT FUNDAMENTAL: The PQM can be programmed to calculate all metering quantities using true
RMS values or the fundamental component of the sampled data. When this setpoint is set to DISABLE, the
PQM will include all harmonic content, up to the 32
this setpoint is set to ENABLE, the PQM will extract the fundamental contribution of the sampled data only
and use this contribution to calculate all metering quantities. Many utilities base their metering upon funda-
mental, or displacement, values. Using the fundamental contribution allows one to compare the quantities
measured by the PQM with the local utility meter.
GE Power Management
SETPOINT
]] SETPOINTS
]] S2 SYSTEM SETUP
MESSAGE
EXTRACT FUNDAMENTAL:
DISABLE
CURRENT DEMAND TYPE:
THERMAL EXPONENTIAL
CURRENT DEMAND TIME
INTERVAL: 30 min
POWER DEMAND TYPE:
THERMAL EXPONENTIAL
POWER DEMAND TIME
INTERVAL: 30 min
ENERGY COST PER kWh:
10.00 cents
TARIFF PERIOD 1
START TIME:
TARIFF PERIOD 1 COST
PER MWH: 10.00 cents
TARIFF PERIOD 2
START TIME:
TARIFF PERIOD 2 COST
PER MWH: 10.00 cents
TARIFF PERIOD 3
START TIME:
TARIFF PERIOD 3 COST
PER MWH: 10.00 cents
nd
harmonic, when making metering calculations. When
PQM Power Quality Meter
4.2 S1 PQM SETUP

4.2.7 CALCULATION PARAMETERS

Range: ENABLE, DISABLE
Range: THERMAL EXPONENTIAL, ROLLING
INTERVAL, BLOCK INTERVAL
Range: 5 to 180 min.; Step: 1 min.
Range: THERMAL EXPONENTIAL, ROLLING
INTERVAL, BLOCK INTERVAL
Range: 0 to 180 min.; Step: 1 min.
Range: 0.01 to 500.00 cents
Step: 0.01 cents
Range: 0 to 1439 min.; Step: 1 min.
0 min.
Range: 0.01 to 500.00 cents
Step: 0.01 cents
Range: 0 to 1439 min.; Step: 1 min.
0 min.
Range: 0.01 to 500.00 cents
Step: 0.01 cents
Range: 0 to 1439 min.
Step: 1 min.
0 min.
Range: 0.01 to 500.00 cents
Step: 0.01 cents
4
4-9