Analog Input; Switch Inputs - GE Power Quality Meter Series Instruction Manual

Table of Contents

Advertisement

4 PROGRAMMING
]] SETPOINTS
]] S2 SYSTEM SETUP
] CURRENT/VOLTAGE
] CONFIGURATION

] ANALOG INPUT

]
] SWITCH INPUT A
]
MESSAGE
MESSAGE
] SWITCH INPUT B
]
MESSAGE
MESSAGE
] SWITCH INPUT C
]
MESSAGE
MESSAGE
] SWITCH INPUT D
]
Figure 4–16: SETPOINTS PAGE 2 – SYSTEM SETUP / SWITCH INPUTS
GE Power Management
SETPOINT
]] SETPOINTS
]] S3 OUTPUT RELAYS
NOTE: Range for Switch A, B, C, D Function (below):
NOT USED, ALARM, AUX 1, AUX 2, AUX 3, NEW DEMAND PERIOD,
SETPOINT ACCESS, SELECT ANALOG OUT, SELECT ANALOG IN, PULSE
INPUT 1, PULSE INPUT 2, PULSE INPUT 3, PULSE INPUT 4, CLEAR
ENERGY, CLEAR DEMAND
SWITCH A NAME:
SWITCH INPUT A
SWITCH A FUNCTION:
NOT USED
SWITCH A ACTIVATION:
OPEN
SWITCH A TIME DELAY:
0.0 s
MESSAGE
SWITCH B NAME:
SWITCH INPUT B
SWITCH B FUNCTION:
NOT USED
SWITCH B ACTIVATION:
OPEN
SWITCH B TIME DELAY:
0.0 s
MESSAGE
SWITCH C NAME:
SWITCH INPUT C
SWITCH C FUNCTION:
NOT USED
SWITCH C ACTIVATION:
OPEN
SWITCH C TIME DELAY:
0.0 s
MESSAGE
SWITCH D NAME:
SWITCH INPUT D
SWITCH D FUNCTION:
NOT USED
SWITCH D ACTIVATION:
OPEN
SWITCH D TIME DELAY:
0.0 s
PQM Power Quality Meter
4.3 S2 SYSTEM SETUP

4.3.4 SWITCH INPUTS

Range: 20 alphanumeric characters
Range: see
above
Range: OPEN, CLOSED
Range: 0.0 to 600.0 s; Step 0.1 s
Range: 20 alphanumeric characters
Range: see
above
Range: OPEN, CLOSED
Range: 0.0 to 600.0 s; Step 0.1 s
Range: 20 alphanumeric characters
Range: see
above
Range: OPEN, CLOSED
Range: 0.0 to 600.0 s; Step 0.1 s
Range: 20 alphanumeric characters
Range: see
above
Range: OPEN, CLOSED
Range: 0.0 to 600.0 s; Step 0.1 s
4
4-27