8.1 DNP 3.0 PROTOCOL
Table 8–1: POINT LIST FOR ANALOG INPUT/OUTPUT CHANGE (Sheet 2 of 5)
POINT
MOBUS
DESCRIPTION
REG
27
02F6
3 Phase Power Factor
28
02F7
Phase A Real Power
29
02F9
Phase A Reactive Power
30
02FB
Phase A Apparent Power
31
02FD
Phase A Power Factor
32
02FE
Phase B Real Power
33
0300
Phase B Reactive Power
34
0302
Phase B Apparent Power
35
0304
Phase B Power Factor
36
0305
Phase C Real Power
37
0307
Phase C Reactive Power
38
0309
Phase C Apparent Power
39
030B
Phase C Power Factor
40
0400
Phase A Current Demand
41
0401
Phase B Current Demand
42
0402
Phase C Current Demand
43
0403
Neutral Current Demand
44
0404
3 Phase Real Power Demand
45
0406
3 Phase React Power Demand
46
0408
3 Phase Apparent Power Demand
47
0440
Frequency
48
0458
Main/Alternate Analog Input
49
0470
Ia Crest Factor
50
0471
Ib Crest Factor
51
0472
Ic Crest Factor
52
0473
Ia Transformer Harmonic Derating
Factor
53
0474
Ib Transformer Harmonic Derating
Factor
8
54
0475
Ic Transformer Harmonic Derating
Factor
55
0478
Phase A Current THD
56
0479
Phase B Current THD
57
047A
Phase C Current THD
58
047B
Neutral Current THD
59
047C
Voltage Van THD
60
047D
Voltage Vbn THD
61
047E
Voltage Vcn THD
62
047F
Voltage Vab THD
see footnote explanations at the end of the table
8-10
UNIT / VALUE
%
1000ths of nominal
1000ths of nominal
1000ths of nominal
%
1000ths of nominal
1000ths of nominal
1000ths of nominal
%
1000ths of nominal
1000ths of nominal
1000ths of nominal
%
1000ths of nominal
1000ths of nominal
1000ths of nominal
1000ths of nominal
1000ths of nominal
1000ths of nominal
1000ths of nominal
0.01x Hz
Unit varies -- 32 bits
0.001 x CF
0.001 x CF
0.001 x CF
0.01 x THDF
0.01 x THDF
0.01 x THDF
0.1 x %
0.1 x %
0.1 x %
0.1 x %
0.1 x %
0.1 x %
0.1 x %
0.1 x %
PQM Power Quality Meter
8 DNP COMMUNICATIONS
DEADBAND
FORMAT
EVENT CLASS
CODE
ASSIGNED TO
5 units
F2
20 units
F4
20 units
F4
20 units
F3
5 units
F2
20 units
F4
20 units
F4
20 units
F3
5 units
F2
20 units
F4
20 units
F4
20 units
F3
5 units
F2
20 units
F1
20 units
F1
20 units
F1
20 units
F1
20 units
F4
20 units
F4
20 units
F3
.05 Hz
F1
10
F3
-
F1
-
F1
-
F1
-
F1
-
F1
-
F1
5.0%
F1
5.0%
F1
5.0%
F1
5.0%
F1
5.0%
F1
5.0%
F1
5.0%
F1
5.0%
F1
GE Power Management
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
2
-
-
-
-
-
-
3
3
3
3
3
3
3
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pqm seriesPqm-t20-c-a

Table of Contents