4 PROGRAMMING
Once setpoint access is enabled, the PROGRAM status indicator turns on. Setpoint alterations are allowed as
long as the PROGRAM status indicator remains on. Setpoint access is be disabled and the PROGRAM status
indicator turns off when:
The time programmed in S1 PQM SETUP \ SETPOINT ACCESS \ SETPOINT ACCESS ON FOR is reached
The control power to the PQM is removed
The factory setpoints are reloaded
To permanently enable the setpoint access feature, enable setpoint access and then set SETPOINT ACCESS ON
FOR to UNLIMITED. Setpoint access remains enabled even if the control power is removed from the PQM.
Setpoints can be changed via the serial ports regardless of the state of the setpoint access feature or
the state of an input switch assigned to setpoint access.
NOTE
To change the setpoint access code, enable setpoint access and perform the steps as outlined below:
CHANGE SETPOINT
ACCESS CODE: YES
If an attempt is made to change a setpoint when setpoint access is disabled, the SETPOINT ACCESS: DISABLED
message is displayed to allow setpoint access to be enabled. Once setpoint access has been enabled, the
PQM display will return to the original setpoint message.
If the control option is installed and one of the switches is assigned to SETPOINT ACCESS, the setpoint access
switch and the software setpoint access will act as a logic AND. That is, both conditions must be satisfied
before setpoint access will be enabled. Assuming the setpoint access switch activation is set to closed, the fol-
lowing flash messages will appear depending upon the condition present when the store key is pressed.
Table 4–1: SETPOINT ACCESS CONDITIONS
CONDITION
ACCESS CODE
SWITCH INPUT
INCORRECT
INCORRECT
CLOSED
CORRECT
CORRECT
CLOSED
GE Power Management
ENTER SETPOINT
ACCESS CODE:
DISPLAYED MESSAGE
SETPOINT ACCESS OFF
OPEN
ENTER ACCESS CODE
SETPOINT ACCESS OFF
ENTER ACCESS CODE
CANNOT ALTER SETTING
OPEN
ACCESS SW. DISABLED
NEW SETPOINT
STORED
PQM Power Quality Meter
4.2 S1 PQM SETUP
RE-ENTER SETPOINT
4
ACCESS CODE:
4
4
S A V C C C D . V S D
4-5