Analog Input Simulation - GE Power Quality Meter Series Instruction Manual

Table of Contents

Advertisement

4 PROGRAMMING
]] SETPOINTS
]] S5 TESTING
] TEST RELAYS & LEDS
]
] CURRENT/VOLTAGE
] SIMULATION
] ANALOG OUTPUTS
] SIMULATION
MESSAGE
MESSAGE
] ANALOG INPUTS
] SIMULATION
Figure 4–37: SETPOINTS PAGE 5 – ANALOG INPUT SIMULATION
SIMULATION: Enter ON to switch from an actual analog input to the programmed simulated value. Set this
setpoint OFF after simulation is complete.
SIMULATION ENABLED FOR: Select the desired length of time that simulation will be enabled. When the
programmed time has elapsed, analog input simulation will turn off. If unlimited is selected, the simulated
analog input will be used until simulation is turned off via the SIMULATION setpoint or via the serial port or
until control power is removed from the PQM.
ANALOG INPUT: Enter an analog input current in the range of 4 to 20 mA to be simulated.
GE Power Management
]] SETPOINTS
]] S1 PQM SETUP
MESSAGE
SIMULATION:
OFF
SIMULATION ENABLED
FOR: 15 min
ANALOG INPUT:
OFF mA
PQM Power Quality Meter
4.6 S5 TESTING

4.6.4 ANALOG INPUT SIMULATION

Range: OFF, ON
Range: 5 to 300, UNLIMITED
Step: 5 min
Range: 4.0 to 20.0, OFF
Step: 0.1 mA
4
4-57

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pqm seriesPqm-t20-c-a

Table of Contents