4 PROGRAMMING
]] SETPOINTS
]] S4 ALARMS/CONTROL
MESSAGE
MESSAGE
] POWER FACTOR
]
Figure 4–28: SETPOINTS PAGE 4 – ALARMS/CONTROL / POWER FACTOR
GE Power Management
SETPOINT
]] SETPOINTS
]] S5 TESTING
MESSAGE
POWER FACTOR LEAD 1
RELAY: OFF
POWER FACTOR LEAD 1
PICKUP ≤ ≤ ≤ ≤ 0.99
POWER FACTOR LEAD 1
DROPOUT ≥ ≥ ≥ ≥ 1.00
POWER FACTOR LEAD 1
DELAY: 10.0 s
POWER FACTOR LAG 1
RELAY: OFF
POWER FACTOR LAG 1
PICKUP ≤ ≤ ≤ ≤ 0.99
POWER FACTOR LAG 1
DROPOUT ≥ ≥ ≥ ≥ 1.00
POWER FACTOR LAG 1
DELAY: 10.0 s
POWER FACTOR LEAD 2
RELAY: OFF
POWER FACTOR LEAD 2
PICKUP ≤ ≤ ≤ ≤ 0.99
POWER FACTOR LEAD 2
DROPOUT ≥ ≥ ≥ ≥ 1.00
POWER FACTOR LEAD 2
DELAY: 10.0 s
POWER FACTOR LAG 2
RELAY: OFF
POWER FACTOR LAG 2
PICKUP ≤ ≤ ≤ ≤ 0.99
POWER FACTOR LAG 2
DROPOUT ≥ ≥ ≥ ≥ 1.00
POWER FACTOR LAG 2
DELAY: 10.0 s
PQM Power Quality Meter
4.5 S4 ALARMS/CONTROL
4.5.5 POWER FACTOR
Range: ALARM, AUX1, AUX2, AUX3, OFF
Range: 0.50 to 1.00, Step 0.01
Range: 0.50 to 1.00, Step 0.01
Range: 0.5 to 600.0; Step 0.5 s
Range: ALARM, AUX1, AUX2,
AUX3, OFF
Range: 0.50 to 1.00, Step 0.01
Range: 0.50 to 1.00, Step 0.01
Range: 0.5 to 600.0; Step 0.5 s
Range: ALARM, AUX1, AUX2,
AUX3, OFF
Range: 0.50 to 1.00, Step 0.01
Range: 0.50 to 1.00, Step 0.01
Range: 0.5 to 600.0; Step 0.5 s
Range: ALARM, AUX1, AUX2,
AUX3, OFF
Range: 0.50 to 1.00, Step 0.01
Range: 0.50 to 1.00, Step 0.01
Range: 0.5 to 600.0; Step 0.5 s
4
4-45