Environmental; Communications; Mechanical Parameters - GE Multilin EPM 6000 Instruction Manual

Multi-function power meter
Hide thumbs Also See for Multilin EPM 6000:
Table of Contents

Advertisement

CHAPTER 1: OVERVIEW
1.4.3

Environmental

1.4.4

Communications

1.4.5

Mechanical Parameters

EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE
ACCURACY
Measured Parameters
Voltage L-N
Voltage L-L
Current
+/– Watts
+/– Wh
+/– vars
+/– varh
VA
VAh
Power Factor (PF)
Frequency
% THD
% Load Bar
NOTE: Typical results are more accurate.
TEMPERATURE AND HUMIDITY
Storage:...............................................................–40 to 85°C
Operating:..........................................................–30 to 70°C
Humidity:............................................................up to 95% RH, non-condensing
Faceplate rating: ............................................NEMA 12 (water resistant), mounting gasket included
COMMUNICATIONS FORMAT
Types:...................................................................RS485 port through back plate
COMMUNICATIONS PORTS
Protocol:..............................................................Modbus RTU, Modbus ASCII, DNP 3.0
Baud rate: ..........................................................9600 to 57600 bps
Port address: ....................................................001 to 247
Data format: .....................................................8 bits, no parity
DIMENSIONS
Size:.......................................................................4.25" × 4.82" × 4.85" (L × W × H)
Mounting: ...........................................................mounts in 92 mm square DIN or ANSI C39.1 4-inch round
Weight: ................................................................2 pounds / 0.907 kg
Shipping..............................................................ships in 6-inch / 152.4 mm cube container
Display Range
0 to 9999 kV or scalable
0 to 9999 V or kV scalable
0 to 9999 A or kA
0 to 9999 W, kW, or MW
5 to 8 digits (programmable)
0 to 9999 vars, kvars, Mvars
5 to 8 digits (programmable)
0 to 9999 VA, kVA, MVA
5 to 8 digits (programmable)
±0.5 to 1.0
45 to 65 Hz
0 to 100%
10 digit resolution scalable
IrDA port through face plate
105.4 mm × 123.2 mm × 123.2 mm (L × W × H)
cut-out
Accuracy
0.1% of reading
0.1% of reading
0.1% of reading
0.2% of reading
0.2% of reading
0.2% of reading
0.2% of reading
0.2% of reading
0.2% of reading
0.2% of reading
0.01 Hz
2.0% F.S.
1 to 120% of reading
1–7