4.5 S4 ALARMS/CONTROL
]] SETPOINTS
]] S4 ALARMS/CONTROL
MESSAGE
MESSAGE

] TIME

]
4
The time function is useful where a general purpose time alarm is required or a process is required to start and
stop each day at the specified time.
TIME RELAY: This setpoint can be used to give an indication (alarm or control) if the programmed PICKUP
TIME is equaled or exceeded. Set to OFF if the feature is not required. Selecting ALARM activates the alarm
relay and displays an alarm message whenever the PQM clock time equals or exceeds the set PICKUP
TIME. Selecting AUX1, AUX2 or AUX3 activates the appropriate auxiliary relay but no message is displayed.
The AUX1, AUX2 and AUX3 selections are intended for process control. The selected relay will de-energize
when the PQM clock time equals or exceeds the DROPOUT TIME setting.
PICKUP TIME: The relay assigned in the TIME RELAY setpoint energizes when the PQM clock time equals
or exceeds the time specified in this setpoint. Follow the example below to set the PICKUP TIME.
PICKUP TIME ≥ ≥ ≥ ≥
12:00:00 am
USE THE VALUE
KEYS TO SELECT THE
U N D E R L I N E D
QUANTITIES
DROPOUT TIME: The relay assigned in the TIME RELAY setpoint de-energizes when the PQM clock time
equals or exceeds the time specified in this setpoint. Follow the example above to set the DROPOUT TIME.
4-52
SETPOINT
MESSAGE
TIME
RELAY: OFF
PICKUP TIME ≥ ≥ ≥ ≥
12:00:00 am
Figure 4–32: SETPOINTS PAGE 4 – ALARMS/CONTROL / TIME
MESSAGE
PICKUP TIME ≥ ≥ ≥ ≥
03:00:00 am
VALUE
PQM Power Quality Meter
]] SETPOINTS
]] S5 TESTING
DROPOUT TIME ≥ ≥ ≥ ≥
12:00:00 pm
MESSAGE
STORE
NEW SETPOINT
STORED
4 PROGRAMMING
4.5.8 TIME
Range: ALARM, AUX1, AUX2, AUX3, OFF
Range: hh:mm:ss am/pm
Range: hh:mm:ss am/pm
PICKUP TIME ≥ ≥ ≥ ≥
03:35:00 am
MESSAGE
PICKUP TIME ≥ ≥ ≥ ≥
03:35:55 am
GE Power Management